Multiquip DCA180SSJU OFF/RESET position, Engine Speed Switch High, Active Fault Code Message

Models: DCA180SSJU

1 106
Download 106 pages 14.07 Kb
Page 53
Image 53
OFF/RESET position.
Preheat Lamp

GENERATOR START-UP PROCEDURE (MANUAL)

When the MPEC Control switch is

NOTE placed in the manual position, preheating of the glow plugs will begin automatically and the preheat lamp will stay lit until

the glow plugs are warmed. When the preheat lamp goes off this signals the completion of the preheating cycle and the starting of the engine.

3.If any abnormalities exists, the Warning and Emergency Stop lamps on the Engine Operating Panel will be lit.

4. Place the

(Figure 43) in the

OFF/RESET position.

 

5.Place the Diagnostic ON/OFF switch in the ON position. Verify that an Active Fault Code message is being displayed (Diagnostic Display Panel). The fault code message will continued to be displayed until the fault has been corrected. Figure 44 shown below is a typical example of an active fault code message (Low Radiator Coolant).

8.

To restart the engine due to error codes, place the

 

in the MANUAL position (Figure 43)

9.

If the engine is running smoothly, place the engine

 

speed switch (Figure 45) in the

(up) position.

Figure 45. Engine Speed Switch (High)

10.Verify that the Engine Running status LED on the MPEC unit (Figure 46) is ON (lit) after the engine has been started.

Figure 46. Engine Running LED (ON)

11.Observe that the Warning and Emergency Stop lamps on the Engine Operating Panel are OFF.

12.The generator's frequency meter (Figure 47) should be displaying the 60 cycle output frequency in HERTZ.

Figure 44. Active Fault Code Message

6.In a situation where several engine problems occur simultaneously, the word “MORE” appears above the arrow buttons indicating that there are more fault codes that need to be viewed. Use the arrow buttons to scroll to the next active fault code.

If desired, the type of fault code, cause of error and the countermeasures of the error can be referenced in a separate engine operator’s manual.

7.Before the engine can be started, the engine fault must be corrected. Also observe that there are no active fault codes displayed on the diagnostic panel. If no fault codes are displayed, place the diagnostic switch in the OFF position.

Figure 47. Frequency Meter (Hz)

13.The generator's AC-voltmeter (Figure 48) will display the generator’s output in VOLTS. If the voltage is not within the specified tolerance, use the voltage adjustment control knob (Figure 49) to increase or decrease the desired voltage.

Figure 48. Voltmeter

DCA-180SSJU — OPERATION AND PARTS MANUAL — REV. #3 (02/01/10) — PAGE 53

Page 53
Image 53
Multiquip DCA180SSJU operation manual OFF/RESET position, Engine Speed Switch High, Active Fault Code Message, Voltmeter