Page 54 |
| WI1424A 1/06 | |
|
| ||
Duress Code. The panel will not allow duplicate User Codes to be programmed. Every user program code may now be | New Operation of the Panel | ||
selected as an Ambush Code for Area 1 or Area 2 by entering a _5 in the Area 1 Options or Area 2 Options respectively. |
|
| |
Note: Keypad(s) must be enabled for Ambush. |
|
| |
Cross Zoning. Required Option for cross zoning with either programmable time period or specified by manufacturer. De- | |||
fault is disabled. The existing programmable by zone feature "Zone ANDing Groups" are available for the cross zoning |
|
| |
option required by |
|
| |
are enable in the Easy Program Menu. Cross Zone set time = one (1) minute. |
|
| |
Swinger Shutdown. Zone will only trip once and will not restore automatically. | |||
1045, 1109, 1173, 1237, 1301 and 1356) and "Swinger Shutdown" (Addresses 0918, 0982, 1046, 1110, 1174, 1238, 1302 |
|
| |
and 1366) are disabled in order to meet the |
|
| |
riod. These features are not selected on zones |
|
| |
|
| ||
|
| ||
down" in this manual. |
|
| |
Fire Alarms. Fire Alarm Verification available option on Fire Zones. Default is disabled. The existing programmable option | |||
"Fire Alarm Verification" is available as required by |
|
| |
abled when "Enable |
|
| |
Call Waiting. Disable Call Waiting on 1st Attempt. Default is disabled. When enabled, the telephone number must | 2053, Bit 5 (see Note 2) | ||
be programmed with *70 in front of the telephone number. The first attempt will dial with *70 (disabling call waiting). | (2053 | · · · · · 6 · ·)* | |
Subsequent attempts (if first attempt is unsuccessful) will dial without *70. Note: The digits used to disable Call | (2053 2 · )** | ||
Waiting may vary with location. Be sure to confirm with local telephone company. Note: Disabling Call Waiting on a |
|
| |
non |
|
| |
System Test. Test Mode for all zones, the sounders, and communicator. The "Fault Find" function (a Function Menu |
|
| |
selection) is enabled, and normally causes all hardwired zones to give a two second beep at the keypad(s) when any |
|
| |
zone is faulted or restored. As required by SIA |
|
| |
tal Dialer Report Enter/Exit Test Mode is programmed. This option is programmed when "Enable | 2053, Bit 4 (see Note 4) | ||
is selected in the Easy Program Menu: | |||
(2053 | · · · · 5 · · ·)* | ||
• When Fault Find is entered, it reports to Central Station that "Test Mode" is in progress. | |||
(2053 1 · )** | |||
• Fault Find can not be initiated from an armed panel, and all digital dialer reporting in same area is inhibited while in | |||
|
| ||
Fault Find. |
|
| |
• Fault Find Central Station Reporting Code is located at address 2053. |
|
| |
• Keypad will display the following warning that the system is in Fault Find: "FAULT FIND RF SIG POWER - - " |
|
| |
• If a |
|
| |
"Faulted" on the keypad display. |
|
| |
• When Fault Find is exited by pressing C, a Fault Find Restore Report will be sent. |
|
|
Notes:
Note 1: This feature is enabled in the factory program and is enabled when "Enable
Note 2: This feature is not enabled in the factory program and is not enabled when "Enable
Note 3: This feature is enabled in the factory program and is enabled when "Enable
Note 4: This feature is programmed when "Enable
•At least one Exit/Entry zone must be programmed for each area. (SIA
•The
•The following optional accessories support the SIA False Alarm Reduction (FAR) classification, and may be used if desired:
•Programming at Installation may be subordinate to other UL requirements for the intended application.
•
•Cross zoning is not recommended for Line security Installations nor is it to be implemented on exit / entry zones.
•There is a Communication Delay of 30 seconds in this control panel. It can be removed, or it can be increased up to 45 seconds at the option of the end user by consulting with the Installer.
•Do not duplicate any reporting codes. This applies for all communication formats other than SIA sending automatic programmed reporting codes.
•In UL installations, Entry Delay time plus Abort Delay time (total combined times) cannot exceed 60 seconds.
•Exit Time Restart must be disabled for UL Line Security/Encryption applications.
*Illustrates the LCD display for the
**Illustrates the LCD display for the
X | LNAPCO Security Systems |