SPECIFICATIONS
Operating Temperature: 0-49°C (32-120°F)
Input Power:
Loop Voltage: 10-13Vdc
Loop Current: 3mA without Zone Doubling, 2.4mA with Zone Doubling using a 2.2K Ohm
Loop Resistance: 300 Ohm max.; 50 Ohm for
Alarm Voltage Output: 1
Programmable Negative Outputs: 2
Auxiliary Power Output: 11.7-12.5 VDC
Remote Power Output: 12 VDC regulated (for keypads)
Combined Standby Current (Remote Power + Aux. Power + Fire Power): See following charts.
RESIDENTIAL BURGLARY & COMMERCIAL BURGLARY**
16.5VAC | BATTERY | STANDBY | ALARM | STANDBY |
TRANSFORMER | (12 VDC) | CURRENT | CURRENT | TIME |
|
|
|
|
|
40VA/50VA | 7 AH | 550 mA | 550 mA(1) | 4 Hours |
20VA* | 7 AH | 500 mA | 2.0 A | 4 Hours |
|
|
|
|
|
20VA* | 7 AH | 500 mA | 2.0 A | 6 Hours |
|
|
|
|
|
|
|
| ||
| COMBINATION RESIDENTIAL FIRE & RESIDENTIAL BURGLARY |
| ||
|
|
|
|
|
16.5VAC | BATTERY | STANDBY | ALARM | STANDBY |
TRANSFORMER | (12 VDC) | CURRENT | CURRENT | TIME |
|
|
|
|
|
40VA/50VA | 7 AH | 120 mA | 520 mA(1) | 24 Hours |
40VA/50VA * | Two 7 AH | 360 mA | 280 mA(1) | 24 Hours |
20VA * | 7 AH | 120 mA | 360 mA(1) | 24 Hours |
20VA * | Two 7 AH | 360 mA | 120 mA(1) | 24 Hours |
NOTE: (1) Alarm current can be increased by reducing standby current by the same amount.
*Not evaluated by UL.
**Commercial Burglary specifications not evaluated by UL.
FOR ALL UL INSTALLATIONS
"ENABLE RESIDENTIAL FIRE" (ADDRESS 1422) MUST BE PROGRAMMED
The feature "Enable Residential Fire" (address 1422, option 4 / bit 3) must be programmed for ALL UL installations. To program, please refer to the
EZM Module:
Keypad Current:
PGM Output: 5mA, 12V Special Application
Maximum Number of Keypads: 7
Maximum Wiring Length for each run (#22AWG): 1000' divided by total number of keypads and
EZMs on run
Keypad Dimensions: 4” x 5” x 1” (HWD); 11.1cm x 14.9cm x 2.7cm (HWD)