Smoke detectors & Summary of UL Requirements

Smoke detectors & Summary of UL Requirements

Page 8

WI1424A 1/06

Smoke Detectors, 4-Wire:

1.ESL 445AT, 445C, 445CT, 445CR, 445CRT

2.Hochiki America SLG-12 with YBC-RL4-RA Base

3.System Sensor 2312/24T; 1412; 1412TH; 2412TH

Subtract total smoke-detector alarm current from available standby current.

Note: Any normally-open devices that do not require power from the control panel, such as pull stations and thermostats may be used if acceptable to the Authority having Jurisdiction.

UL Compatible Smoke Detectors (Providing UL Recognition or Listing)

Manufacturer

 

4-Wire

 

2-Wire

Smoke Detector

 

Smoke Detector

Smoke Detector *

Base

 

 

 

 

 

 

Napco

 

FW-4

 

FW-2

 

 

 

 

 

 

 

Sentrol

449AT

449CLT

712U

731U

701U

 

449C

449CSLT

722U

 

702U

 

449CRT

449CTE

732U

 

702RE

 

449CST

741U

711U

 

702RU

 

449CSRT

742U

721U

 

 

 

449CSRH

 

721UT

 

 

 

449CSST

 

 

 

 

 

 

 

 

 

 

System

1112

2112T

2100

1100

 

Sensor

2112

2112TSRB

2100T

 

 

 

 

 

 

 

 

Note: * Voltage Rating: 8.5-13.3 VDC, Maximum Number of Detectors: 10

SUMMARY OF UL REQUIREMENTS

Residential

Recognized Limited-Energy Cable for initiating, indicating and supplementary circuits.

Initiating loops supervised if longer than 3 feet

FT2200 End-of-Line Relay for Fire (if using 4-wire smoke detectors)

Minimum alarm timeout of 5 minutes

Maximum exit time: 60 seconds

Maximum entry time: 45 seconds

Do not program “Swinger Shutdown”, “Force Arming”, “Selective Bypass” or “50 ms Loop Response”

“Abort Delay” may not exceed 45 seconds

Program “Disable Callback Download”

Automatic dialer may not dial a police station number that has not been dedicated for such service

System must be tested at least weekly under AC/battery and Battery-Only conditions

Replace the rechargeable battery at least every 5 years

If the battery is heavily discharged, replace it or have it tested by a qualified technician

For silent panic, connect only to UL-listed holdup devices

All zones must be programmed for “Priority”

Do not program any zones for “Keyswitch Arming”

System must be serviced at least once every year

Residential Fire and Combination Residential Fire & Burglary must program “Residential Fire”

Keypad Expansion (EZM) Zones are not to be used as fire zones

Keypad Auxiliary is not to be selected

The GEM-K Series Keypads must have the indicators printed on the face label (Fire, Police and Auxiliary) covered by a supplied label if not in use.

X GEM-P1664 Installation Instructions

LNAPCO Security Systems

Page 8