KEYPAD CONFIGURATION MODE

WI1424A 1/06

Page 17 

KEYPAD CONFIGURATION MODE

This section will focus on configuring the GEM-RP1CAe2/GEM-K1CA and GEM-RP2ASe2/GEM-K2AS Keypads. We recommend that either a GEM-RP1CAe2 or a GEM-K1CA keypad be used for programming.

KEYPAD INSTALLATION

Each keypad must be assigned an address number (1–7) and each requires its own configuration procedure (see CONFIGURING THE KEYPADS, which follows, and DIRECT ADDRESS KEYPAD AREA OPTIONS). At least 1 keypad must be used; only 1 is required for a single-area Commercial Burglary installation.

GEM-RP1CAe2/GEM-K1CA- is a 2-line combination fire/burglary/access keypad capable of supporting 4 EZM zones. A GEM- RP1CAe2 or GEM-K1CA is recommended for use with programming.

GEM-RP2ASe2/GEM-K2AS- is a utility LCD keypad combining several preset LCD words with a limited message line. NOTE: Due to space constraints, available messages are abbreviated and will scroll automatically.

CONFIGURING THE KEYPADS

A total of up to 7 keypads may be connected to the panel. GEM-RP1CAe2/GEM-K1CA and GEM-RP2ASe2/GEM-K2AS keypads may be intermixed but require different configuration procedures, as described in the following paragraphs. If you have a GEM-K1CA key- pad, please see the "Important Note" on page 5 regarding the differences between the GEM-RP1CAe2 and the GEM-K1CA keypad buttons. The buttons displayed below will be for the GEM-K1CA keypad.

Configuring the GEM-RP1CAe2/GEM-K1CA Keypad

Each GEM-RP1CAe2/GEM-K1CA keypad must be configured for (a) keypad tactile beep; (b) entry

 

sounder; (c) keypad address; (d) EZM address; and (e) zone response.

NORMAL

To enter the GEM-RP1CAe2/GEM-K1CA Configuration Mode:

KEYPAD

1. Move jumper JP1 (located at the upper center of the control panel board) from Pins 1-2 (top two) to

CONFIGURE

Pins 2-3 (bottom two). NOTE: See the Wiring Diagram.

 

2.After about 15 seconds, the display will read “XX OUT OF SYSTEM”, where XX indicates the keypad address.

3.Press 11123Rand proceed as follows. (Repeat the following procedure for all keypads.)

Keypad Configuration

Keypad Beep

ON

Keypad Tactile Beep

Upon entering the Keypad Configuration Mode, “KEYPAD BEEP ON” will be displayed, indicating that the tactile beep, which sounds when any button is pressed, is on.

To turn off the tactile beep, press the Uor Dbutton (the Uor Dbutton will

toggle the tactile beep on and off). Press the Aor Rbutton to continue or press the Cbutton to exit.

Mode

Entry Sounder

Entry Sounder

ON

To turn off the keypad sounder during entry time, press the Uor Dbutton (the

 

Uor Dbutton will toggle the entry sounder on and off). Press the Aor

 

Rbutton to continue or press the Cbutton to exit.

Keypad Address

Keypad Address

01

If more than one keypad is installed, each must be assigned a unique keypad

 

address (that is, no two keypads may be numbered alike):

 

 

keypads must be numbered consecutively (missing numbers are not

 

permitted)

To assign the keypad number, proceed as follows:

1.Enter the assigned keypad number 01–07, then press the Uor Dbutton to save. A valid number will be acknowledged by a short beep; an invalid number will be rejected by a long beep.

2.Press the Aor Rbutton to continue or press the Cbutton to exit.