3.5VENTING APPLICATION FLOW CHART

14

3.5VENTING APPLICATION FLOW CHART

TOP EXIT

Horizontal Termination

 

 

Vertical Termination

 

 

 

 

 

 

 

 

 

 

 

Vertical rise is equal

to or greater than the horizontal run

Horizontal run +

vertical rise to

maximum of 40 feet

Vertical rise is less than horizontal run

Horizontal run +

vertical rise to

maximum of 24.75

feet

4.2times the

vertical rise equal to or greater than the horizontal run

Vertical rise is equal

to or greater than the horizontal run

Horizontal run +

vertical rise to

maximum of 40 feet

Vertical rise is less than horizontal run

Horizontal run +

vertical rise to

maximum of 40 feet

3 times the vertical

rise equal to or greater than the horizontal run

13.1

3.6DEFINITIONS

For the following symbols used in the venting calculations and examples are:

>- greater than

>- equal to or greater than < - less than

< - equal to or less than

HT - total of both horizontal vent lengths (Hr) and offsets (Ho) in feet HR - combined horizontal vent lengths in feet

HO - offset factor: .03 (total degrees of offset - 90°*) in feet VT - combined vertical vent lengths in feet

14.1

3.7ELBOW VENT LENGTH VALUES

 

FEET

INCHES

0.03

0.5

15°

0.45

6.0

30°

0.9

11.0

45°

1.35

16.0

90°*

2.7

32.0

* The first 90° offset has a zero value and is shown in the formula as - 90°