SECTION 4 OPERATION AND CALIBRATION

SECTION 4 OPERATION AND CALIBRATION

Important: These changes must be performed by a qualified technician.

WARNING: Do not connect ac power to your meter until you have completed all input and output connections. Failure to do so may result in injury!

1.Wire the meter according to the wiring section. This includes power, thermocouple and analog signal connections.

2.Apply power to the meter and the display will show the temperature of the probe.

The meter is shipped from the factory calibrated to the accuracy as specified. No re-calibration is necessary. In the event that there is a desire to check the calibration, the following procedure is given.

4.1EQUIPMENT REQUIRED

¥Meter

¥a small screwdriver

¥a precision resistance source in 0.01¡ resolution or ÒDecade Box".