CS-TE9DKE CU-TE9DKE / CS-TE12DKE CU-TE12DKE

9.3.2.Dry Operation9.3.2.1.Thermostat Control

••[Intake Air Temp. - Remote Controller Setting Temp.] > [Thermostat-OFF Temp. +0.5 °C]

Operated in corresponding frequency.

••Frequency is decided after a completion of the starting control (in 60 seconds).

••When Room Temp. is below [Thermostat-OFF Temp.] continuously for 3 minutes or more, it turns to Thermostat- OFF operation.

••When room temperature almost comes to Thermostat-OFF Temp., the operation turns to the Minimum power & fan speed: SSLo.

9.3.3.Heating Operation9.3.3.1.Thermostat Control

••[Intake Air Temp. - Remote Controller Setting Temp.] > [Thermostat-OFF Temp. +0.5 °C]

Operated in corresponding frequency.

••Frequency is decided after a completion of starting control (in 60 seconds).

••When Room Temp. is below Thermostat-OFF Temp. continuously for 3 minutes or more, it turns to Thermostat- OFF operation.

••When room temperature almost comes to Thermostat-OFF Temp., the operation turns to the Maximum power.

Dry

Power

TE9DKE

TE12DKE

Intake Air Temp.

Maximum

2.7kW

4.0kW

Difference (°C)

Rated

2.5kW

3.6kW

 

Intermediate

~

~

 

Minimum

0.8kW

0.8kW

(-2.50)

OFF

Heating

Power

TE9DKE

TE12DKE

Intake Air Temp.

OFF

Difference (°C)

Minimum

0.8kW

0.8kW

 

Intermediate

~

~

 

Rated

3.5kW

4.5kW

(+1.00)

Maximum

4.6kW

6.2kW

22