WHEN INSTALLING AN AIR CONDITIONAL, BE SURE TO EVACUTE THE AIR INSIDE THE INDOOR UNIT AND PIPES in the following procedure.
1.Connect a charging hose with a push pin to the Low and High side of a charging set and the service port of the
••Be sure to connect the end of the charging hose with the push pin to the service port.
2.Connect the center hose of the charging set to a vacuum pump with check valve, or vacuum pump and vacuum pump adaptor.
3.Turn on the power switch of the vacuum pump and make sure that the needle in the gauge moves form 0 cmHg (0 MPa) to - 76cm Hg
4.Close the Low and High side valve of the charging set the turn off the vacuum pump. Make sure that the needle in the gauge does not move after approximately 5 minutes.
Note: BE SURE TO FOLLOW THIS PROCEDURE INORDER IN ORDER TO AVOID REFRIGERANT GAS LEAKAGE.
5.Disconnect the charging hose from vacuum pump and from the service port of the
6.Tighten the service port caps of the
7.Remove the valve caps of both of the
8.Mount valve caps onto the
••Be sure to check for gas leakage.
Caution
••If gauge needle does not move from 0 cmHg (0 MPa) to
••If the leag stops when the piping connections are tightened further, continue working form step 3.
••If the leak does not stop when the connections are retightened, repair the location of leak.
••Do not release refrigerant during piping work for installation and reinstallation. Take care of the liquid refrigerant, it may cause frostbite.
47