9.9.Timer Operation (24H Real Timer)
••
••Both
An example of
An example of
Preliminary operation
••Unit operates preliminarily until room temperature reaches setting temperature on
••Indoor and outdoor fans operate for 30 seconds in 70 minutes before setting time and sampling of outdoor air and intake air temperatures is performed.
••Fan speed and airflow directions in preliminary operation are based on remote controller setting. (Same condition as in normal operation.)
••In preliminary operation, deicing judgment is performed after heating operated for 15 minutes in 50 minutes before setting
Deicing Judgment: Deicing operation (Max. 12 minutes) will be performed when outdoor air temperature is below 0°C, if outdoor heat exchanger temperature of below 0°C continues for 14 minutes and below
Preliminary operation in Cooling or Dry mode
Outdoor | Air | Intake | Air | Operation | |
Temperature |
| Temperature | Starting Time |
| |
35 °C or more |
| — | Before 15 min. | ||
— |
| 30 °C or more | Before 15 min. | ||
30 - 35 °C |
| 25 - 30 °C | Before 10 min. | ||
Below 30 °C |
| Below 25 °C | Before 5 min. | ||
Preliminary operation in Heating mode |
| ||||
Outdoor | Air | Intake | Air | Operation | |
Temperature |
| Temperature | Starting Time |
| |
5 °C or more |
|
| — | Before 40 min. | |
— |
| 15 °C or more | Before 40 min. | ||
0 - 5 °C |
| 5 - 15 °C | Before 45 min. | ||
Below 0 °C |
| Below 5 °C | Before 50 min. |
9.10. Auto Restart Control
1.When the power supply is cut off during the operation of air conditioner, the compressor will
2.This type of control is not applicable during ON/OFF Timer setting.