9.11. Ionizer Operation

9.11.1. Negative Ion Generator

Display and operation for the Negative Ion Generator remain unchanged for ION only operation and simultaneous ION operation.

Refer to the ION operation described below.

Single blinking of the ION LED does not indicate Breakdown.

••When unit was operated under the condition that a discharge insulation of the Ion Cleaning equipment is deteriorated (Dust, Attached water, etc.):

1.If the insulation deterioration of the unit discharge part is small;

When air cleaning abnormal status is detected in 1 minute or more from the unit starts operating, the unit is OFF for 10 minutes.

↑↓ (The ION LED and CLEAN monitor light up.) The unit is ON in 5 minutes. (Repeating)

2.If the insulation deterioration of the unit discharge part is big;

When air cleaning abnormal status is detected within 1 minute from the unit starts operating, the unit is shut OFF immediately and the ION LED blinks.

3.If the insulation of the Ionizer is deteriorated;

When abnormal status is detected, the unit is OFF for 30 minutes. When abnormal status is detected 25 times, the operation stops and the ION LED blinks. (It will be reset if normal status continues for 10 minutes before reaching 25 times.)

To cancel it, stop the operation while the ION LED is blinking.

Note: Set ION Air Cleaning operation again because it is canceled when re-operated.