Panasonic CU-KE36NKU, CU-KE30NKU, CS-KE30NKU service manual CS-KE36NKU

Models: CS-KE30NKU CS-KE36NKU CU-KE30NKU CU-KE36NKU

1 112
Download 112 pages 47.47 Kb
Page 24
Image 24
Manual background

Indoor Unit

: CS-KE36NKU

 

 

 

 

 

 

 

 

Outdoor Unit

: CU-KE36NKU

 

 

 

 

 

 

 

 

Power Supply : 230V Single Phase 60Hz

 

 

 

 

 

 

 

 

< Cooling Capacity >

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

RATING CAPACITY:

34,000 BTU/h

 

AIR FLOW RATE:

630 CFM

 

INDOOR

 

 

 

OUTDOOR

 

 

 

ENT. TEMP. oF (oC)

 

 

AMBIENT TEMP. oF (oC)

 

 

 

WB

DB

 

65

75

85

95

105

115

 

 

 

 

(18.3)

(23.9)

(29.4)

(35.0)

(40.6)

(46.1)

 

 

 

TC

27,450

28,140

28,840

29,040

24,650

16,770

 

 

72 (22.2)

SHC

19,680

20,050

20,410

20,530

18,210

14,420

 

59

76 (24.4)

SHC

22,000

22,370

22,740

22,860

20,530

16,740

 

(15.0)

80 (26.7)

SHC

24,450

24,820

25,180

25,300

22,980

16,770

 

 

84 (28.9)

SHC

26,770

27,140

27,510

27,630

24,650

16,770

 

 

88 (31.1)

SHC

27,450

28,140

28,840

29,040

24,650

16,770

 

 

 

TC

35,010

34,360

33,600

33,100

24,850

16,910

 

 

72 (22.2)

SHC

20,170

19,800

19,310

19,070

15,030

11,480

 

63

76 (24.4)

SHC

22,490

22,120

21,760

21,390

17,360

13,810

 

(17.2)

80 (26.7)

SHC

24,940

24,570

24,200

23,840

19,800

16,250

 

 

84 (28.9)

SHC

27,260

26,890

26,530

26,280

22,120

16,910

 

 

88 (31.1)

SHC

29,580

29,220

28,850

28,610

24,450

16,910

 

 

 

TC

35,720

35,120

34,400

#

34,000

24,930

16,970

 

 

72 (22.2)

SHC

16,620

16,380

16,010

15,890

11,730

8,670

 

67

76 (24.4)

SHC

19,070

18,700

18,330

18,210

14,180

11,000

 

(19.4)

80 (26.7)

SHC

21,510

21,150

20,900

20,660

16,620

13,440

 

 

84 (28.9)

SHC

23,840

23,590

23,230

22,980

18,940

15,770

 

 

88 (31.1)

SHC

26,160

25,920

25,550

25,300

21,270

16,970

 

 

 

TC

36,270

35,710

35,040

34,780

24,870

16,950

 

 

72 (22.2)

SHC

13,070

12,830

12,460

12,340

8,430

5,610

 

71

76 (24.4)

SHC

15,400

15,150

14,790

14,790

10,750

7,940

 

(21.7)

80 (26.7)

SHC

17,840

17,600

17,360

17,230

13,200

10,380

 

 

84 (28.9)

SHC

20,170

19,920

19,680

19,560

15,520

12,710

 

 

88 (31.1)

SHC

22,490

22,250

22,000

21,880

17,840

15,030

 

 

 

TC

36,560

36,070

35,450

34,630

24,680

16,830

 

75

76 (24.4)

SHC

11,850

11,610

11,360

11,120

7,570

5,130

 

(23.9)

80 (26.7)

SHC

14,300

14,050

13,810

13,560

10,020

7,570

 

 

84 (28.9)

SHC

16,620

16,500

16,250

15,890

12,340

9,900

 

 

88 (31.1)

SHC

18,940

18,820

18,580

18,210

14,660

12,220

TC : Total Cooling Capacity (BTU/h) SHC : Sensible Heat Capacity (BTU/h)

NOTE

1.Rating conditions (#) : Indoor Unit Entering Air Temp. 80 °F (26.7 °C) DB / 67 °F (19.4 °C) WB

:Outdoor Ambient Temp. 95 °F (35 °C) DB

2.Above data does not take Freeze Prevention Protection during cooling operation into account. For this reason, the value may vary from the actual cooling characteristics.

3.Above data represents the value when the operation frequency of a compressor is fixed.

24