Panasonic CU-KE36NKU, CU-KE30NKU CS-KE36NKU, Voltage:230V, Cooling, Heating, Voltage:208V

Models: CS-KE30NKU CS-KE36NKU CU-KE30NKU CU-KE36NKU

1 112
Download 112 pages 47.47 Kb
Page 32
Image 32

Indoor Unit

CS-KE36NKU

 

 

 

 

Outdoor Unit

CU-KE36NKU

 

 

 

 

(1) Voltage:230V

 

 

 

 

 

 

Cooling

 

 

 

 

 

 

< 230V >

 

 

 

 

 

 

 

 

 

 

 

 

 

Indoor

UnitOutdoor Unit

Complete Unit

 

 

 

 

 

 

 

 

 

 

 

 

Fan Motor

Fan Motor + Compressor

 

 

 

 

 

 

 

 

 

 

 

 

 

Performance at

 

 

 

 

230V Single-phase 60Hz

 

 

 

 

 

 

 

 

Rating conditions

 

Running amp.

A

0.4

19.6

20.0

 

 

 

 

 

 

 

 

 

 

 

Power input

W

39

3,961

4,000

 

 

 

 

 

 

Rating conditions:

Indoor air temperature:

80 °F (26.7 °C) DB / 67 °F (19.4 °C) WB

 

 

 

Outdoor air temperature:

95 °F (35 °C) DB

 

 

Heating

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Indoor

UnitOutdoor Unit

Complete Unit

 

 

 

 

 

 

 

 

 

 

 

 

Fan Motor

Fan Motor + Compressor

 

 

 

 

 

 

 

 

 

 

 

 

 

Performance at

 

 

 

 

230V Single-phase 60Hz

 

 

 

 

 

 

 

 

Rating conditions

 

Running amp.

A

0.5

17.7

18.2

 

 

 

 

 

 

 

 

 

 

 

Power input

W

43

3,607

3,650

Rating conditions:

Indoor air temperature

70 °F (21.1 °C) DB

 

 

 

 

Outdoor air temperature

47 °F (8.3 °C) DB / 43 °F (6.1 °C) WB

 

(2) Voltage:208V

 

 

 

 

 

 

Cooling

 

 

 

 

 

 

< 208V >

 

 

 

 

 

 

 

 

 

 

 

 

 

Indoor

UnitOutdoor Unit

Complete Unit

 

 

 

 

 

 

 

 

 

 

 

 

Fan Motor

Fan Motor + Compressor

 

 

 

 

 

 

 

 

 

 

 

 

 

Performance at

 

 

 

 

208V Single-phase 60Hz

 

 

 

 

 

 

 

 

Rating conditions

 

Running amp.

A

0.4

21.5

21.9

 

 

 

 

 

 

 

 

 

 

 

Power input

W

39

3,961

4,000

Rating conditions:

Indoor air temperature:

80 °F (26.7 °C) DB / 67 °F (19.4 °C) WB

 

 

 

Outdoor air temperature:

95 °F (35 °C) DB

 

 

Heating

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Indoor

UnitOutdoor Unit

Complete Unit

 

 

 

 

 

 

 

 

 

 

 

 

Fan Motor

Fan Motor + Compressor

 

 

 

 

 

 

 

 

 

 

 

 

 

Performance at

 

 

 

 

208V Single-phase 60Hz

 

 

 

 

 

 

 

 

Rating conditions

 

Running amp.

A

0.5

19.4

19.9

 

 

 

Power input

W

43

3,607

3,650

Rating conditions:

Indoor air temperature

70 °F (21.1 °C) DB

 

 

 

 

Outdoor air temperature

47 °F (8.3 °C) DB / 43 °F (6.1 °C) WB

 

32

Page 32
Image 32