Panasonic CS-KE30NKU, CU-KE36NKU, CS-KE36NKU service manual Cooling Capacity, CU-KE30NKU

Models: CS-KE30NKU CS-KE36NKU CU-KE30NKU CU-KE36NKU

1 112
Download 112 pages 47.47 Kb
Page 23
Image 23
5-2. Cooling Capacity

5-2. Cooling Capacity

Indoor Unit

: CS-KE30NKU

 

 

 

 

 

 

 

 

Outdoor Unit

: CU-KE30NKU

 

 

 

 

 

 

 

 

Power Supply : 230V Single Phase 60Hz

 

 

 

 

 

 

 

 

< Cooling Capacity >

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

RATING CAPACITY:

30,600 BTU/h

 

AIR FLOW RATE:

630 CFM

 

INDOOR

 

 

 

OUTDOOR

 

 

 

ENT. TEMP. oF (oC)

 

 

AMBIENT TEMP. oF (oC)

 

 

 

WB

DB

 

65

75

85

95

105

115

 

 

 

 

(18.3)

(23.9)

(29.4)

(35.0)

(40.6)

(46.1)

 

 

 

TC

26,540

27,120

27,710

27,910

24,890

17,310

 

 

72 (22.2)

SHC

19,190

19,430

19,800

19,920

18,330

14,660

 

59

76 (24.4)

SHC

21,510

21,880

22,120

22,250

20,660

16,990

 

(15.0)

80 (26.7)

SHC

23,960

24,330

24,570

24,690

23,100

17,310

 

 

84 (28.9)

SHC

26,280

26,650

26,890

27,020

24,890

17,310

 

 

88 (31.1)

SHC

26,540

27,120

27,710

27,910

24,890

17,310

 

 

 

TC

31,580

30,910

30,160

29,630

25,270

17,560

 

 

72 (22.2)

SHC

18,330

17,970

17,600

17,360

15,150

11,730

 

63

76 (24.4)

SHC

20,660

20,290

19,920

19,680

17,480

14,050

 

(17.2)

80 (26.7)

SHC

23,100

22,740

22,370

22,120

20,050

16,500

 

 

84 (28.9)

SHC

25,430

25,060

24,690

24,450

22,370

17,560

 

 

88 (31.1)

SHC

27,750

27,510

27,020

26,770

24,690

17,560

 

 

 

TC

32,420

31,780

31,050

#

30,600

25,550

17,760

 

 

72 (22.2)

SHC

15,150

14,790

14,420

14,300

12,100

8,920

 

67

76 (24.4)

SHC

17,480

17,110

16,870

16,620

14,420

11,240

 

(19.4)

80 (26.7)

SHC

19,920

19,560

19,310

19,070

16,870

13,690

 

 

84 (28.9)

SHC

22,250

22,000

21,640

21,390

19,190

16,010

 

 

88 (31.1)

SHC

24,570

24,330

23,960

23,710

21,510

17,760

 

 

 

TC

33,130

32,540

31,840

31,490

25,710

17,880

 

 

72 (22.2)

SHC

11,730

11,480

11,120

11,000

8,670

5,860

 

71

76 (24.4)

SHC

14,050

13,810

13,440

13,320

11,120

8,310

 

(21.7)

80 (26.7)

SHC

16,500

16,250

15,890

15,770

13,560

10,750

 

 

84 (28.9)

SHC

18,820

18,580

18,330

18,210

15,890

13,070

 

 

88 (31.1)

SHC

21,150

20,900

20,660

20,530

18,210

15,400

 

 

 

TC

33,630

33,090

32,430

32,190

25,730

17,900

 

75

76 (24.4)

SHC

10,750

10,510

10,260

10,140

7,940

5,370

 

(23.9)

80 (26.7)

SHC

13,200

12,950

12,710

12,590

10,380

7,820

 

 

84 (28.9)

SHC

15,520

15,280

15,030

15,030

12,710

10,140

 

 

88 (31.1)

SHC

17,840

17,720

17,480

17,360

15,030

12,590

TC : Total Cooling Capacity (BTU/h) SHC : Sensible Heat Capacity (BTU/h)

NOTE

1.Rating conditions (#) : Indoor Unit Entering Air Temp. 80 °F (26.7 °C) DB / 67 °F (19.4 °C) WB

:Outdoor Ambient Temp. 95 °F (35 °C) DB

2.Above data does not take Freeze Prevention Protection during cooling operation into account. For this reason, the value may vary from the actual cooling characteristics.

3.Above data represents the value when the operation frequency of a compressor is fixed.