Panasonic CU-KE36NKU, CU-KE30NKU Defrost detection and release, CT Peak current cut-offcontrol

Models: CS-KE30NKU CS-KE36NKU CU-KE30NKU CU-KE36NKU

1 112
Download 112 pages 47.47 Kb
Page 40
Image 40
 Defrost detection and release

Defrosting Sequence Defrost detection and release

 CT (Peak current cut-off control) Reverse-Cycle Defrosting

Defrosting Sequence

Heating operation

Manual background Outdoor fan ON Manual background 4-way valve ON

Frost sensing

Defrost detection occurs in either of the following cases:

The temperature of the heat exchanger remains at or below the L1 line for 3 minutes after the start of HEAT operation.

The temperature of the heat exchanger remains at or below the L2 line for 120 minutes after the start of HEAT operation.

Outdoor heat

exchanger temp.

0

Ambient temp.

L2

L1

Frosting area

Reverse-cycle defrosting operation

Manual background Compressor Manual background 1 minute after it is stopped, compressor is ON.

Manual background Outdoor fan Manual background OFF

Manual background Indoor fan Manual background OFF

Manual background 4-way valve Manual background OFF

Manual background Operation lamp Manual background Repeatedly switches between red and orange illumination.

Releasing of defrosting

Manual background Outdoor heating exchanger temp. is over 57.2°F (14°C).

Manual background Defrosting operation lasts 12 minutes (maximum). 2 minutes after it is stopped, compressor is ON.

4-way valve is ON. Outdoor fan is ON.

NOTE

If the air conditioner is turned off during the defrosting cycle, it will continue defrosting and turn itself off after defrosting is completed.

Manual background CT (Peak current cut-off control)

This function prevents the circuit breaker or fuse from operating to open the circuit. This function works when electrical current

has increased due to an increase in the cooling / heating load, or to a decrease in the power supply voltage. In these cases, operation frequency is reduced or operation is interrupted auto- matically to control the electrical current for operation.

When the cause of the increase in electrical current is rectified, the system will resume operation in the original mode.

< CS-KE30NKU >

 

 

(A)

 

Cooling

Dry

Heating

Peak current cut-off trips

 

25.0

 

Hz down

 

22.0

 

< CS-KE36NKU>

 

 

(A)

 

Cooling

Dry

Heating

 

 

 

 

Peak current cut-off trips

 

25.0

 

Hz down

24.0

 

23.5

NOTE Electrical current setting for COOL operation is used during DEFROST operation.

40

Page 40
Image 40
Panasonic CU-KE36NKU, CU-KE30NKU Defrost detection and release, CT Peak current cut-offcontrol, Defrosting Sequence