( Continued from the previous page A. )

( Continued from the previous page A. )

( Continued from the previous page B. )

A

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

B

 

 

 

Yes

 

 

 

Is the voltage of about DC22V to

 

 

 

 

 

 

24V given between the terminals

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

2 and 3 on the indoor unit terminal strip

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

(Serial Communication Line) ?

 

 

 

 

 

 

 

 

 

 

 

 

 

 

(Fig. 2)

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

No

 

Defect or connection error

 

 

 

 

 

Defect in the indoor unit

 

in the inter-unit cable

 

 

 

 

 

 

 

P.C. board

 

 

 

 

 

 

 

 

 

 

 

 

Outdoor Unit

1. Turn OFF the power and wait until the power lamp (LED)

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

of the outdoor unit controller is turned OFF.

 

 

 

 

1

2

 

3

4

5

6

 

2. Short-circuit between the terminals 2 and 3 on the outdoor

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

unit terminal strip.

(Fig. 3)

 

 

 

 

 

 

 

 

 

 

Power

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

1

2

 

3

 

 

 

 

 

 

 

 

 

 

 

Indoor Unit

1. Turn ON the power and operate the system using the

 

 

 

 

Fig. 3

remote controller or the operation button on the indoor unit.

 

 

 

 

2.Perform the self-diagnosis five seconds after the operation start.

Alarm Code : E07/P04/P05/

What is the latest self-diagnosis result ?

P20/P27

 

 

 

Defect in the outdoor unit

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

P.C. board.

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Alarm Code : E05

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Outdoor Unit

 

 

 

 

 

 

 

Outdoor Unit

1. Turn off the power and wait until the power lamp (LED)

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

of the outdoor unit controller is turned OFF.

 

 

1

2

3

4

5

6

 

1

2

3

4

5

6

 

2. Remove the short-circuit between the terminals 2 and 3 on

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

the outdoor unit terminal strip.

 

 

 

 

 

 

 

 

 

Power

 

 

 

 

 

 

 

 

Power

 

 

 

 

 

 

 

 

 

 

 

 

3. Disconnect the cable from the terminal 3 on the indoor unit

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

terminal strip.

(Fig. 4)

 

1

2

3

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

1

2

3

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Short-circuit between the terminals 2 and 3 on the indoor unit

terminal board.

(Fig. 5)

Indoor Unit

Indoor Unit

Fig. 4

Fig. 5

1.Turn ON the power and operate the system using the remote controller or the operation button on the indoor unit.

2.Perform the self-diagnosis five seconds after the operation start.

Alarm Code : E07/P04/P05/

P20/P27

What is the latest self-diagnosis result ?

Alarm Code : E05

Defect in the indoor unit

P.C. board

Defect or connection error

in the inter-unit cable

46