8. TROUBLESHOOTING (BEFORE CALLING FOR SERVICE)

8-1. Precautions before Performing Inspection or Repair

After checking the self-diagnostics monitor, turn the power OFF before starting inspection or repair.

High-capacity electrolytic capacitors are used inside the outdoor unit controller (inverter). They retain an electrical charge (charging voltage DC 310V) even after the power is turned OFF, and some time is required for the charge to dissipate. Be careful not to touch any electrified parts before the controller LED (red) turns OFF.

If the outdoor controller is normal, approximately 30 seconds will be required for the charge to dissipate. However, allow at least 5 minutes for the charge to dissipate if there is thought to be any trouble with the outdoor controller.

8-2. Method of Self-Diagnostics

Follow the procedure below to perform detailed trouble diagnostics.

NOTE

1:If the operation lamp blinks every 0.5 seconds immediately when the power is turned ON, there is an external ROM (OTP data) failure on the indoor circuit board, or a ROM socket insertion problem, or the ROM has not been installed.

2:The failure mode is stored in memory even when the power is not ON. Follow the procedure below to perform diagnostics.

PROCEDURE

After turning on power to the air conditioner, use the remote controller and follow the steps below to execute self-diagnostics.

Step 1: Press and hold the remote controller QUIET button and 1 HR TIMER button. Then, press and hold the ACL (reset) button with a pointed object such as the tip of a pen. After 5 seconds, release ACL button first, then release QUIET and 1 HR TIMER buttons, "oP-1" (test run) appears, blinking in the remote controller clock display area.

Step 2: Next, press the 1 HR TIMER button twice to change the display from "oP-1" to "oP-2" and "oP-3" (self-diagnostics). (The display continues to blink.)

Step 3: Finally press the ON/OFF button to engage self-diagnostics mode.

The self-diagnostics function utilizes the 3 indicator lamps on the main unit, in combinations of ON lamps, blinking lamps, and OFF lamps, to report the existence of sensor trouble or a protective operation. (The lamps blink or remain ON for 5 seconds, then turn OFF for 2 seconds.) Self-diagnostics is completed when the buzzer sounds 3 short beeps.

A maximum of 3 self-diagnostics reports are displayed, for 5 seconds each, beginning with the most recent report. Following this display the lamps turn OFF. In order to view the self-diagnostics results again, press the ON/OFF button again.

The 3 lamps remain OFF if no trouble has occurred.

<IMPORTANT> After self-diagnostics is completed, be sure to press the ACL (reset) button to return to normal mode. The air conditioner will not operate if this is not done.

QUIET button

<Clock display > Test run mode

Deletion of self-diagnostics report mode

Self-diagnostics mode

ON/OFF operation button

1HR.

TIMER button

ACL (Reset) button

41

Page 41
Image 41
Panasonic CU-KE30NKU Troubleshooting Before Calling for Service, Precautions before Performing Inspection or Repair

CS-KE30NKU, CS-KE36NKU, CU-KE30NKU, CU-KE36NKU specifications

The Panasonic CU-KE36NKU, CS-KE36NKU, CU-KE30NKU, and CS-KE30NKU air conditioning units represent the brand's commitment to delivering high-performance cooling solutions backed by innovative technologies. These units cater to both residential and commercial applications, ensuring users experience maximum comfort throughout the year.

One of the standout features of these models is their energy efficiency. Both units are equipped with advanced inverter technology, which allows for variable speed operation. This means they can adjust their power output according to the room's cooling needs, reducing energy consumption and minimizing electric bills while maintaining a consistent temperature. The models boast impressive SEER (Seasonal Energy Efficiency Ratio) ratings, making them environmentally friendly options.

Panasonic's nanoe-G technology is another remarkable feature incorporated into these models. This technology helps to purify the air by generating hydroxyl radicals, which eliminate airborne particles, odors, and harmful bacteria. This results in a healthier indoor environment, conducive to both comfort and well-being. The air purification aspect not only enhances the air quality but also extends the lifespan of the HVAC system by reducing the buildup of dust and contaminants.

In terms of user convenience, both the CU-KE and CS-KE series are equipped with programmable timers, allowing users to set their desired operation schedules. They also come with a remote control for ease of use, enabling adjustments from a distance. The installation process is straightforward, and the sleek design blends seamlessly with various interior aesthetics, making them a suitable choice for any room.

Durability is a key characteristic of Panasonic air conditioning units, and the CU-KE36NKU, CS-KE36NKU, CU-KE30NKU, and CS-KE30NKU are designed to withstand varying environmental conditions. Their robust construction ensures reliability and performance over the years. Additionally, both models come with a quiet operation feature that minimizes noise levels, allowing for comfortable use without disturbing daily activities.

In summary, the Panasonic CU-KE36NKU, CS-KE36NKU, CU-KE30NKU, and CS-KE30NKU are exceptional air conditioning units that combine energy efficiency, innovative purification technology, user-friendly features, and robust durability. These models are an ideal investment for anyone seeking a reliable and high-performance cooling solution.