Pelco ES31PC Pressurized Integrated Optics Cartridge, Alert Label Cycle, Alert Reset, Condition

Models: ES31PC ES30PC

1 70
Download 70 pages 33.09 Kb
Page 15
Image 15
PRESSURIZED INTEGRATED OPTICS CARTRIDGE

PRESSURIZED INTEGRATED OPTICS CARTRIDGE

The pressurized IOC houses an auto focus camera, lens, heater, and sensors in a self-contained, sealed unit. Dry nitrogen pressurized to 10 psig controls the environment inside the cartridge, eliminating internal condensation and corrosion.

Sensors strategically placed inside the pressurized IOC continually monitor pressure, temperature, and relative humidity. If internal conditions reach unacceptable levels, an alert label appears on the screen describing the alert condition. Example: If pressure drops below 1 psig, LOW PRESSURE is displayed on the monitor.

The following conditions will trigger an alert:

CONDITION

ALERT LABEL

 

 

1 psig

Low Pressure

 

 

25 psig

High Pressure

 

 

-40°C

Low Temperature

 

 

60°C

High Temperature

 

 

20%

High Relative Humidity

 

 

ALERT LABEL CYCLE

The Esprit system continually checks internal environmental conditions every 60 seconds. An ALERT label appears on the monitor if conditions are beyond manufacturer set acceptable limits. The label will be repeatedly displayed until acknowledged by the system controller. Once acknowledged, alert behavior changes to the programmed acknowledge action. If the alert condition remains unacceptable after a period of time, the ALERT label will reappear on the monitor, restarting the alert label cycle. The cycle will continue until the alert condition is resolved.

ALERT LABEL

DISPLAYED ON

MONITOR

CYCLE REPEATS UNTIL

CONDITION IS RESOLVED

ALERT CONDITION

NOT RESOLVED

REPEAT

USER DEFINED REFER

ALERT LABEL IS

TO REPEAT IN THE

DISPLAYED ON MONITOR

PROGRAMMING

UNTIL ACKNOWLEDGED

SECTION OF THIS

BY CONTROLLER

MANUAL

 

ACK ALERT

ALERT ACKNOWLEDGED

ACK ACT

ONCE ACKNOWLEDGED

USER DEFINED REFER

ALERT LABEL BEHAVIOR

TO ACK ACT IN THE

CHANGES TO THE ACTIVE

PROGRAMMING

SECTION OF THIS

RESPONSE PROGRAMMED

MANUAL

FOR ACK ACT

 

ALERT CONDITION

LABEL OFF

RESOLVED

ALERT RESET

The Alert Reset function clears alert conditions and removes the ALERT label. The system will automatically check internal environmental conditions 60 seconds after reset. If conditions remain beyond manufacturer set acceptable limits, the ALERT label will reappear on the screen indicating further corrective action is required.

C311M-N (6/06)

15

Page 15
Image 15
Pelco ES31PC, ES30PC manual Pressurized Integrated Optics Cartridge, Alert Label Cycle, Alert Reset, Condition