186
Serial Port Profiles
Embedded When this option is selected, the address of the slave Modbus device is
embedded in the message header.
Default: Enabled
Remapped Used for single device/port operation. Older Modbus devices may not include a
UID in their transmission header. When this option is selected, you can specify
the UID that will be inserted into the message header for the Modbus slave
device. This feature supersedes the Broadcast feature.
Default: Disabled
Remap UID Specify the UID that will be inserted into the message header for the Slave
Modbus serial device.
Range: 1-247
Default: 1
Enable IP Aliasing When enabled, allows for multiple requests to serial slaves (from an Ethernet
Master/s) to be processed simultaneously.
Default: Off
See IP Address for details about setting the IP address to be used with this
serial port.
Enable SSL/TLS
using global
settings
When enabled, Modbus Slave Gateway messages to remote TCP Modbus
Masters are encrypted via SSL/TLS.
Default: Disabled