Installation

 

Powerware 9150 Hardwired Terminations for Optional PDM

 

 

 

 

 

 

Wire Function

Terminal

Upstream

Suggested Wire Size**

Conduit Connection

 

Input

Position*

Circuit Breaker

(Entry Size)

 

 

 

 

 

 

 

 

 

 

Ground

TB1-1

 

8 AWG

 

 

 

 

 

 

L1/A

TB1-2

70A

4 AWG

1-3/42access hole for

 

 

 

 

L2/B

TB1-3

70A

4 AWG

1-1/42conduit

 

 

 

 

 

Neutral

TB1-4

 

2 AWG

 

 

 

 

 

 

Output for PDM

 

 

Wire Color

 

 

 

 

 

 

Ground

TB1-6

 

Green/Yellow

 

 

 

 

 

 

L1/A

TB1-7

 

Black

1-3/42access hole for

 

 

 

 

L2/B

TB1-8

 

Red

1-1/42conduit

 

 

 

 

 

Neutral

TB1-9

 

White

 

 

 

 

 

 

*All terminal wire size ratings are 8 - 4 AWG, except TB1-4 is 8 - 1/0.

**Use 75C copper wire. Suggested wire size is based on 120/208 full load ratings applied to NEC Code Table 310-16.

NOTE Proper phase rotation must be observed.

1

2

3

4

6

7

8

9

Ground L1/A L2/B

N

Ground L1/A L2/B

N

 

Input

 

 

Output

 

 

 

 

 

 

 

Figure 11. Hardwired Terminal Blocks

Powerware® 9150 User’s Guide : www.powerware.com

29