Installation
| Powerware 9150 Hardwired Terminations for Optional PDM |
| |||
|
|
|
|
| |
Wire Function | Terminal | Upstream | Suggested Wire Size** | Conduit Connection | |
| |||||
Input | Position* | Circuit Breaker | (Entry Size) | ||
| |||||
|
|
|
| ||
|
|
|
|
| |
Ground |
| 8 AWG |
| ||
|
|
|
|
| |
L1/A | 70A | 4 AWG | |||
|
|
|
| ||
L2/B | 70A | 4 AWG | |||
|
|
|
|
| |
Neutral |
| 2 AWG |
| ||
|
|
|
|
| |
Output for PDM |
|
| Wire Color |
| |
|
|
|
|
| |
Ground |
| Green/Yellow |
| ||
|
|
|
|
| |
L1/A |
| Black | |||
|
|
|
| ||
L2/B |
| Red | |||
|
|
|
|
| |
Neutral |
| White |
| ||
|
|
|
|
|
*All terminal wire size ratings are 8 - 4 AWG, except
**Use 75•C copper wire. Suggested wire size is based on 120/208 full load ratings applied to NEC Code Table
NOTE Proper phase rotation must be observed.
1 | 2 | 3 | 4 | 6 | 7 | 8 | 9 |
Ground L1/A L2/B | N | Ground L1/A L2/B | N | ||
| Input |
|
| Output |
|
|
|
|
|
|
|
Figure 11. Hardwired Terminal Blocks
Powerware® 9150 User’s Guide : www.powerware.com | 29 |