Troubleshooting

Indicator or Alarm

Possible Cause

Action

 

 

 

ALARM

1 short and 4 long beeps indicate a neutral

 

On or Blinking

fault.

 

10 short and 5 long beeps indicate a neutral

Input Neutral must be connected. Contact

fault at startup.

qualified service personnel (such as a licensed electrician).

7 short and 1 long beep indicates a neutral fault at shutdown.

ALARM blinking

REPO initiated.

3 short beeps and 1

 

long beep.

 

The circuit connected to the REPO connector

 

 

is open and preventing UPS operation.

None. The UPS remains off until the REPO switch is turned back on.

Check that the REPO connector is in place and that the circuit connected to it forms a closed loop. Contact your service representative if the condition persists.

ALARM

Battery failure. Battery voltage dropped too

On or Blinking

fast and too low after charging.

5 short beeps and 4

 

long beeps.

 

 

 

Verify the battery circuit breaker(s) are turned on. If the condition persists, the batteries may need replacing. Contact your service representative.

ALARM

Input phase error.

Input phases must be rotated. Contact qualified

On or Blinking

 

service personnel (such as a licensed electrician).

11 short beeps and 5

 

 

long beeps.

 

 

 

 

 

Silencing the Alarm

Press the RESET pushbutton on the LED panel to silence and reset the alarm.