Troubleshooting
Indicator or Alarm | Possible Cause | Action |
|
|
|
ALARM | 1 short and 4 long beeps indicate a neutral |
|
On or Blinking | fault. |
|
10 short and 5 long beeps indicate a neutral
Input Neutral must be connected. Contact
fault at startup.
qualified service personnel (such as a licensed electrician).
7 short and 1 long beep indicates a neutral fault at shutdown.
ALARM blinking | REPO initiated. | |
3 short beeps and 1 |
| |
long beep. |
| |
The circuit connected to the REPO connector | ||
| ||
| is open and preventing UPS operation. |
None. The UPS remains off until the REPO switch is turned back on.
Check that the REPO connector is in place and that the circuit connected to it forms a closed loop. Contact your service representative if the condition persists.
ALARM | Battery failure. Battery voltage dropped too |
On or Blinking | fast and too low after charging. |
5 short beeps and 4 |
|
long beeps. |
|
|
|
Verify the battery circuit breaker(s) are turned on. If the condition persists, the batteries may need replacing. Contact your service representative.
ALARM | Input phase error. | Input phases must be rotated. Contact qualified |
On or Blinking |
| service personnel (such as a licensed electrician). |
11 short beeps and 5 |
|
|
long beeps. |
|
|
|
|
|
Silencing the Alarm
Press the RESET pushbutton on the LED panel to silence and reset the alarm.
56 | Powerware® 9150 User’s Guide : www.powerware.com |