
Operation
Isolated Alarm Relay InterfaceThe isolated alarm relay interface uses a
| 1 | 2 | 3 | 4 | 5 | 6 | 7 | 8 |
|
| 9 | 10 | 11 | 12 | 13 | 14 | 15 |
| Figure 21. | |||||||
| Relay Interface of Powerware 9150 | |||||||
| Pin No. Connection | System State |
|
|
| |||
Utility Failure | 1 - 2 Closed | Line normal |
|
|
| |||
| 1 - 3 Closed | Line failure |
|
|
| |||
Low Battery | 4 - 5 Closed | Battery normal |
|
|
| |||
| 4 - 6 Closed | Battery low |
|
|
| |||
UPS on Bypass | 10 - 11 Closed | On UPS |
|
|
|
| ||
| 10 - 12 Closed | On Bypass |
|
|
|
| ||
UPS On or | 7 - 9 Closed | UPS on |
|
|
|
| ||
UPS Alarm | 7 - 8 Closed | UPS alarm |
|
|
|
| ||
UPS Shutdown | 13 - 15 Closed | UPS shutdown when operating in Battery Mode. UPS can be shut down | ||||||
(in Battery Mode only) |
| by sending a | ||||||
|
| connecting Pin 15 to Pin 13. This signal must be present for a minimum | ||||||
|
| of 5 seconds. |
|
|
|
NOTE The relay contacts are rated for a maximum 1A/30 Vac or 0.2A/60 Vdc. All relay outputs are isolated from the other circuits of the UPS. The relay contacts must not be connected to any utility connected circuits. Reinforced insulation to the utility is required.
Powerware® 9150 User’s Guide : www.powerware.com | 49 |