Operation

 

 

ON

 

 

OFF

UPS ON/OFF Switch

 

CB2

and Indicators

 

(Optional)

F1

CB1

External

Battery

Internal

Battery

Neutral

Battery

 

Fuse

 

 

Maintenance

Bypass Switch

Figure 17. UPS Breakers and Switches (Front Panel Removed)

Using the Maintenance Bypass Switch

The Maintenance Bypass switch is standard on all Powerware 9150 models and is used to bypass the UPS during maintenance or servicing. The Maintenance Bypass switch is located behind the front panel. The SERVICE position on the Maintenance Bypass switch allows a service engineer to apply power to the UPS input and verify its operation while the load is powered through bypass.

44

Powerware® 9150 User’s Guide : www.powerware.com