Installation
Manual Configuration ModeTo change the nominal output voltage and frequency from the front panel:
1.If the UPS is operating in Normal Mode, turn off the UPS
ON/OFF switch (the position). Then press and hold the RESET pushbutton on the LED panel while turning on the UPS ON/OFF switch (the position). Continue to hold the RESET pushbutton until the LEDs begin to cycle right to left and then release.
2.One of the LEDs remains blinking. The blinking LED shows the current configuration according to the following table.
Blinking LED | Configuration | ||
|
| ||
Input/Output Voltage | Output Frequency | ||
| |||
|
|
| |
ALARM | 120/208V | 50 Hz | |
|
|
| |
SERVICE | 110/220V | 50 Hz | |
|
|
| |
OVERTEMP | 127/220V | 50 Hz | |
|
|
| |
OVERLOAD | 100/200V | 50 Hz | |
|
|
| |
80% | 120/240V | 50 Hz | |
|
|
| |
60% | 120/208V | 60 Hz | |
|
|
| |
40% | 110/220V | 60 Hz | |
|
|
| |
LOAD | 127/220V | 60 Hz | |
|
|
| |
BYPASSED | 100/200V | 60 Hz | |
|
|
| |
ON BATTERY | 120/240V | 60 Hz |
3.Press the RESET pushbutton quickly to scroll through the configuration options. Each time you press the button, the next LED blinks.
4.When the correct setting is blinking, press and hold the RESET pushbutton until the alarm beeps twice (approximately three seconds). The UPS indicates successful configuration by sequencing all the LEDs.
Powerware® 9150 User’s Guide : www.powerware.com | 37 |