C H A P T E R 5

SPECIFICATIONS

Powerware 9150 Technical Specifications

Rated Power

Technology

Input Voltage Range

Input Power Factor

Input Rated Voltage

Input Frequency Range

Input Rated Frequency

Nominal/Maximum Input

Output Voltage

Output Voltage Regulation

Output Voltage Distortion

Output Frequency

Output Frequency Regulation

Output Overcurrent

8 kVA, 10 kVA, 12.5 kVA at 0.7 power factor

Online, double-conversion topology with Static Bypass switch and 3-position Maintenance Bypass switch.

Frequency independent operation.

85 - 146 Vac per phase

0.95 typical

100/200, 110/220, 120/240 Vac 180phase displacement 120/208, 127/220 Vac 120phase displacement

45 - 65 Hz

50/60 Hz selectable, auto-configuring

8kVA 10 kVA

12.5 kVA

100/200, 110/220, 120/240 Vac 180phase displacement 120/208,127/220 Vac 120phase displacement

50/60 Hz selectable, auto-configuring

2% static

5% dynamic at 100% load change Response time 1 ms

<2 % THD linear load

<5 % THD non-linear load

50/60 Hz, selectable or auto-configuring

Synchronization to line, 0.5, 1.0 or 2.0 Hz selectable

Free-running: 0.005 Hz

Slew rate 1.0, 2.0 or 3.0 Hz/second selectable

>112.5 - 150% for 30 seconds >150% for 0.3 seconds

Powerware® 9150 User’s Guide : www.powerware.com

51