Operation
5 | 4 | 3 | 2 | 1 | 1 | 2 | 3 | 4 | 5 |
9 |
| 8 | 7 | 6 | 6 |
| 7 | 8 | 9 |
Female Connector | Male Connector | ||||||||
(OnliNet or ConnectUPS) | (LanSafe III/FailSafe III or Modem) | ||||||||
Figure 20.
Use the female connector for a computer running OnliNet software or for a ConnectUPS Adapter. The communication settings are 19200 baud, 1 start bit, 8 data bits, No parity, and 1 stop bit. See the following table for pin assignments.
Pin 1 Received data
Pin 2 Transmitted data
Pin 3 AC input failure, closing to Pin 4
Pin 4 Signal ground
Pin 5 Impending battery low, closing to Pin 4
Pin 8 +DC auxiliary power
Pin 9 Chassis ground
Use the male connector for a computer running LanSafe III/FailSafe III software or for a modem connection. The communication settings are 1 start bit, 8 data bits, No parity, 1 stop bit, and XON/XOFF. The baud rate is
Pin 1 Data carrier detected
Pin 2 Received data
Pin 3 Transmitted data
Pin 4 Data terminal ready
Pin 5 Signal ground
Pin 7 Ready to send
48 | Powerware® 9150 User’s Guide : www.powerware.com |