Specifications

Environmental and Safety Specifications

Ambient Temperature

Ventilation

Altitude

Humidity

Audible Noise

Safety

EMC/RFI

Surges

0C to + 40C operating

+15C to +25C recommended

-10C to +40C storage with batteries -10C to +50C without batteries

Fan cooling, temperature uP monitored

3,281 ft (1000 m) operating without derating

41,012 ft (12500 m) during transportation

5 - 95% RH, noncondensing

<55 dBA at 1 meter distance UL 1778, cUL

FCC class A

ANSI/IEEE C62.41-1991

External Battery Cabinet Specifications

 

EBC-48

EBC-96

 

 

 

DC-voltage

288V

288V

 

 

 

Batteries

48 x 7 Ah

96 x 7 Ah

 

 

 

Weight

468 lb (213 kg)

765 lb (348 kg)

 

 

 

Width

15.752 (400 mm)

15.752 (400 mm)

 

 

 

Depth

28.942 (735 mm)

28.942 (735 mm)

 

 

 

Height

28.462 (723 mm)

28.462 (723 mm)

 

 

 

54

Powerware® 9150 User’s Guide : www.powerware.com