Powerware 9315 UPS operation manual Bypass Mode

Models: 9315 UPS

1 84
Download 84 pages 17.95 Kb
Page 19
Image 19

Understanding UPS Operation

3.2 Bypass Mode

The UPS automatically switches to Bypass mode if it detects an overload, load fault, or internal failure. The bypass source supplies the commercial AC power to the load directly.

C A U T I O N

The critical load is not protected while the UPS is in Bypass mode.

Figure 3-2shows the path of electrical power through the UPS system when the UPS is operating in Bypass mode.

Bypass Input

Rectifier Input

Rectifier

CB1

Bypass

K4

Inverter

K3

Output

(Open)

Transformer

Path of electrical power

Battery

Figure 3-2. Path of Current Through the UPS in Bypass Mode

You can transfer the UPS from Normal mode to Bypass mode manually. However, the UPS switches automatically to Bypass mode whenever the inverter can no longer supply the critical load. If the UPS transfers to Bypass mode from Normal mode due to any reason other than operator intervention, the UPS automatically attempts to transfer back to Normal mode (up to three times within a 10-minute period). The fourth transfer will lock the critical load on the bypass source and requires operator intervention to transfer.

Bypass mode is a normal operating mode, and not an alarm condition. However, if the UPS is unable to return to Normal mode following an automatic transfer to Bypass mode, an alarm condition is recorded.

EATON Powerware® 9315 UPS (200–300 kVA) Operation Manual S 164201036 Rev G www.powerware.com

3−3

Page 19
Image 19
Powerware 9315 UPS operation manual Bypass Mode