Product Specifications

Table 9-3. System Output

Rectifier/Charger Capacity

125%

 

 

DC Filtering

Ripple voltage less than 0.5% peak to peak

 

 

UPS Output Capacity

100% rated current

 

 

Output Voltage Regulation

1% (10% to 100% load)

 

 

Output Voltage Adjustment

208 Vac nominal, adjustable from 198 Vac to 218 Vac (60 Hz only)

(Nominal +/–5%)

480 Vac nominal, adjustable from 456 Vac to 504 Vac (60 Hz only)

 

600 Vac nominal, adjustable from 570 Vac to 630 Vac (60 Hz only)

 

400 Vac nominal, adjustable from 380 Vac to 420 Vac (50/60 Hz)

Output Voltage Harmonic Content

3% max THD, 2% max single (linear load)

 

 

Output Voltage Balance

3% for 100% maximum load imbalance

 

 

Output Voltage Phase

3° for 100% maximum load imbalance

Displacement

 

 

 

Output Transients

"5% for 100% load step or removal

 

 

Frequency Regulation

"0.01 Hz free running

 

 

Synchronous to Bypass

Bypass within voltage limits of +5%, –8% of output setting; bypass within

 

±0.5 Hz

 

 

Frequency Slew Rate

1 Hz per second maximum (adjustable)

 

 

Overload Capability

125% for 10 minutes

 

150% for 10 seconds

 

 

Maximum Output Capability

300% peak for 10 cycles without bypass

Table 9-4. Environmental Specifications

 

 

Operating Temperature

0 to 40°C without derating. However, operating at or near 40°C will

 

adversely affect battery life (refer to your battery specifications for more

 

information). The recommended operating temperature is 25°C.

 

 

Operating Altitude

Maximum 1500m (5000 ft) at 40°C without derating

 

 

Storage Temperature

–20 to +70°C (prolonged storage above 40°C will cause rapid battery

 

self-discharge)

 

 

Relative Humidity (operating and

95% maximum noncondensing

storage)

 

 

 

Acoustical Noise

65 dBA at a 1m distance

 

 

EMI Suppression

Meets FCC Regulation 47, Part 15, Subpart J, for class A devices

 

 

Electrostatic Discharge (ESD)

Meets IEC 801-2 specifications. Withstands up to 25 kV without damage and

Immunity

with no disturbance or adverse effect to the critical load.

 

 

9−2

EATON Powerware® 9315 UPS (200–300 kVA) Operation Manual S 164201036 Rev G www.powerware.com

Page 72
Image 72