Using the Monitor Panel
AGraphics − Displays a
ASetup − Allows you to configure the UPS communication port and set the date and time for the timestamp.
Figure 5-3 shows the LCD screen as it appears when you first start the UPS. The Meters menu is displayed in the menu box, with the System option highlighted. In the information area, the system meters show their current readings.
|
| Uninterruptible Power System |
|
|
|
| |||||
System Normal |
|
|
|
|
|
| 04 MAY 1997 | 14:23:45 | |||
Alarm: | None |
|
|
|
|
|
|
|
|
|
|
Notice: None |
|
|
|
|
|
|
|
|
|
| |
Battery |
| Input |
|
|
| Output |
| ||||
Percent |
|
|
|
|
| ||||||
|
|
|
|
|
|
|
|
|
| ||
100% | VAB | VBC | VCA | FREQ | VAB | VBC | VCA | FREQ | |||
|
| ||||||||||
|
| 480 | 480 | 480 | 60.0 | 480 | 480 | 480 | 60.0 | ||
|
| IA | IB |
|
| IC | IA | IB | IC | IN | |
|
| 480 | 480 |
| 480 | 361 | 361 | 361 | 000 | ||
|
| KVA | KW |
|
| PF |
| KVA | KW | PF |
|
|
| 399 | 379 | 0.95 |
| 300 | 240 | 0.80 | |||
Meters |
|
|
|
|
|
|
|
|
|
| |
System |
| Bypass |
|
|
| Battery |
| ||||
Load Amps |
|
|
|
|
|
|
|
|
|
| |
|
| VAB | VBC |
| VCA |
| V |
| I |
| |
|
| 480 | 480 |
| 480 |
| 540 |
| 000 |
| |
Meters | Events | Statistics Graphics | Setup |
|
|
|
|
|
Figure 5-3. System Meters Screen (Typical for Powerware 9315 300 480/480V UPS)
The Input area shows the phase-to-phase voltage, frequency, and phase current of the incoming utility, followed by the kVA, KW, and power factor measurements. The output area shows the same information for the power being output by the UPS.
The Bypass area shows the phase-to-phase voltage of the bypass source. The Battery area displays the DC voltage (V) and the DC current (I).
Select Load Amps from the Meters menu to see a real-time bar graph of the output current of the UPS. The graph shows the current for each phase.
Figure 5-4 shows the Load Amps Meters screen.
EATON Powerware® 9315 UPS | 5−5 |