Starting and Stopping the UPS
The following describes the switches on the Control Panel (see Figure
AThe MODE switch is a
−Place the critical load in Bypass mode when the UPS is operating in Normal mode and the bypass source is within acceptable limits. If the transfer does not occur within two seconds, an alarm sounds.
−Prevent transfer to Normal mode when the UPS is in Bypass mode.
−Shut down the power processing unit (inverter and rectifier) of the UPS.
AThe BATTERY switch is a
AThe circuit breaker (CB1) switch controls the operation of the rectifier and inverter. If CB1 is on (closed), the rectifier turns on when the START switch is activated and the proper voltage is at the input terminals.
AThe PUSH TO RESET button is described in page 11−2.
AThe START switch activates the power controls on the Control Panel. The START switch is
The following sections describe how to operate these controls to start, stop, or change the operating mode of the UPS.
4.1.1To Place the UPS in Normal Mode
1.Close the Input Power Feeder breaker.
2.Verify that the Load Off PUSH TO RESET button is pressed in.
3.Turn the BATTERY switch to NORMAL.
4.Turn the MODE switch to NORMAL.
5.Move the CB1 switch to ON.
6.Turn the START switch to the right momentarily.
The rectifier turns on, then the inverter turns on. The UPS display and alarm alert you to close the battery breaker.
7.Close the battery breaker(s).
4−2 | EATON Powerware® 9315 UPS |