Communication

7.6.3 Meters Printout – [Ctrl]+[M]

This key sequence prints the current readings of the UPS system meters. The input area shows the phase-to-phase voltage, frequency, and phase current of the incoming utility, followed by the kVA, kW, and power factor measurements. The output area shows the same information for the power being output by the UPS. The Bypass area shows the phase-to-phase voltage of the bypass source. The Battery area displays the DC voltage (V) and the DC current (I). Figure 7-7shows a sample Meters printout.

 

 

Uninterruptible Power System

UPS System Normal

 

03 JAN 1997 14:22:49

Alarm:

None

 

 

 

 

 

 

 

Notice:

None

 

 

 

 

 

 

 

 

 

Input

 

Output

 

VAB

VBC

VCA FREQ

VAB

VBC

VCA

FREQ

480

480

480 60.0

480

480

480

60.0

 

IA

IB

IC

IA

IB

IC

 

IN

 

480

480

480

361

361

361

0

 

KVA

KW

PF

 

KVA

KW

 

PF

 

399

379

0.95

 

300

240

0.80

 

 

Bypass

 

Battery

 

VAB

VBC

VCA

 

V

+

 

I

 

480

480

480

 

540

 

 

0

Figure 7-7. System Meters

EATON Powerware® 9315 UPS (200–300 kVA) Operation Manual S 164201036 Rev G www.powerware.com

7−11

Page 57
Image 57
Powerware 9315 UPS operation manual Meters Printout Ctrl+M, System Meters