Powerware 9315 UPS operation manual Configuring the Serial Ports

Models: 9315 UPS

1 84
Download 84 pages 17.95 Kb
Page 52
Image 52

Communication

7.5 Configuring the Serial Ports

You must configure the port for communication using the LCD screen and buttons on the UPS Monitor Panel.

Select Port 1 from the Setup menu to display one of the Setup Port screens. The screens for Port 1 and Port 2 are identical, and allow you to specify settings for the two serial communication ports. Figure 7-5shows the Setup Serial Port 1 screen.

NOTE You should configure only Port 1 unless field service has performed a wiring change for Port 2.

 

 

Uninterruptible Power System

 

 

UPS System Normal

 

 

 

03 NOV 1997

14:23:45

Alarm:

None

 

 

 

 

 

 

Notice: None

 

 

 

 

 

 

Battery

 

 

 

 

 

 

Percent

 

 

 

 

 

 

100%

 

Setup Serial Port 1

 

 

 

 

 

 

 

Mode

Rate

Data/Stop

Handshaking

Save

 

 

TERMINAL

9600

8

1

XON / XOFF

NO

Setup

 

 

 

 

 

 

Port 1

 

 

 

 

 

 

Port 2

 

 

 

 

 

 

Time

 

 

 

 

 

 

 

Meters

Events

Statistics Graphics

Setup

 

 

 

 

Figure 7-5. Setup Serial Port 1 Screen

A small return arrow () appears in the upper right corner of the Setup Port screen. This

arrow is a reminder that you can press the button on the Monitor Panel to toggle the buttons between the menu box and the information area.

If the scroll bar is in the menu box, press the button to toggle to the information area. The first setting (Mode) is highlighted. Press the or button to move the highlight to the setting you want to change. To scroll through the available options for that setting, press the or button.

To save the settings upon exit from this screen, be sure the Save field is set to YES.

7−6

EATON Powerware® 9315 UPS (200–300 kVA) Operation Manual S 164201036 Rev G www.powerware.com