Powerware 9315 UPS operation manual Nominal Battery

Models: 9315 UPS

1 84
Download 84 pages 17.95 Kb
Page 73
Image 73

Product Specifications

These specifications are for batteries supplied by the UPS manufacturer in line-up–and–match cabinets:

Table 9-5. Battery Specifications

Battery Type

Sealed, maintenance-free, high rate discharge, lead-acid cells

 

 

Nominal Battery

480 Vdc (240 cells) for Powerware 9315 225 and Powerware 9315 300

String Voltage

420 Vdc (210 cells) for Powerware 9315 200 and Powerware 9315 250

 

 

Float Charging

2.25 Vdc per cell

 

(540 Vdc based on 240 cells)

 

(470 Vdc based on 210 cells)

 

 

Equalizing Charge

2.40 Vdc per cell, set to 2.25 Vdc at factory

 

 

Battery Charge

Limited to 25% of full, regardless of actual load on inverter

Current Limit

 

 

 

EATON Powerware® 9315 UPS (200–300 kVA) Operation Manual S 164201036 Rev G www.powerware.com

9−3

Page 73
Image 73
Powerware 9315 UPS operation manual Nominal Battery