Communication

7.6 Terminal Mode

In this mode, system events are continually logged through the serial port to the device connected to the port. Port 2 operates by default in Terminal mode.

The printed log entries contain a time and date stamp and the alarm text message. Terminal mode uses this format for printing alarm entries:

MMM DD HH:MM:SS.hh KYWD MESSAGE

:::: <CR> <LF>

Symbol

Description

 

MMM

Month (3 letters)

 

DD

Day (2 digits)

 

HH

Hour (2 digits)

 

MM

Minute (2 digits)

 

SS

Second (2 digits)

 

hh

Hundredths of Second (2 digits)

KYWD MESSAGE

Keyword (ALARM, NOTICE, COMMAND, or STATUS)

::::System Diagnostic Information

<CR>

Carriage Return Character (ASCII 13)

<LF>

Line Feed (ASCII 10)

An alarm message is prefixed by the word

Event History Log with a cleared status.

7.6.1 Printing Selected Information

If a port is operating in Terminal mode and is connected to a computer, you can use key combinations at any time to print only selected information:

[Ctrl]+[P] Prints the entire log with a header

[Ctrl]+[M] Prints the current system meters with a header [Ctrl]+[A] Prints all system information

[Ctrl]+[B] Prints the Battery Test Log

To use a key combination, hold down the Control key and press the letter key.

EATON Powerware® 9315 UPS (200–300 kVA) Operation Manual S 164201036 Rev G www.powerware.com