Chapter 9

Product Specifications

The UPS systems are housed in freestanding, double-front cabinets with safety shields behind the doors. The UPS systems are available in 50/60 Hz with various output power ratings. Smaller models within a system may be upgraded in the field to larger models:

Table 9-1. Model Numbers

System

Models

Notes

 

 

 

Powerware 9315 300

225 and 300 kVA

60 Hz only

 

 

 

Powerware 9315 250

200 and 250 kVA

50/60 Hz (400V models only)

 

 

 

Powerware 9315 225

225 kVA

60 Hz only

 

 

 

Powerware 9315 200

200 kVA

50/60 Hz (400V models only)

 

 

 

The following sections detail the input, output, environmental, and battery specifications for the UPS.

Table 9-2. System Input

Operating Input

480 Vac for operation from 408 Vac to 528 Vac (60 Hz only)

Voltage

400 Vac for operation from 340 Vac to 440 Vac (50/60 Hz only)

(Nominal +10/–15%)

600 Vac for operation from 510 Vac to 660 Vac (60 Hz only)

 

 

Operating Input

"3 Hz of nominal (50 Hz or 60 Hz)

Frequency Range

 

 

 

Operating Input

Battery Charge

Current

125% of full load for overload + battery charge

 

Actual load + 25% of full load for battery charge with 0.8 pF

 

output units

 

115% of full load for overload + battery charge

 

Actual load + 15% of full load for battery charge with 0.9 pF

 

output units

 

Reduced for Generator

 

Adjustable, set to 102%

 

 

Input Current

10% THD at full load (with input filter option installed)

Harmonic Content

 

 

 

Power Walk-In

Adjustable 3–60 second rectifier ramp-up to full utility load

 

 

Power Factor

Minimum 0.95

 

 

Line Surges

6 kV OC, 3 kA SC per ANSI 62.41 and IEC 801-4

 

 

EATON Powerware® 9315 UPS (200–300 kVA) Operation Manual S 164201036 Rev G www.powerware.com