Communication

Table 7-2.Pin Assignments for Port 2 (DB-25)

Pin Number

Symbol

Function

Comments

 

 

 

 

1

GND

Chassis Ground

 

 

 

 

 

2

TXD

Transmit Data

Input to UPS

 

 

 

 

3

RXD

Receive Data

Output from UPS

 

 

 

 

4

RTS

Request to Send

Input to UPS

 

 

 

 

5

CTS

Clear to Send

Output from UPS

 

 

 

 

6

DSR

Data Set Ready

Output from UPS

 

 

 

 

7

RTN

Return

 

 

 

 

 

8

+12V

+12 Volts

Output from UPS - always true

 

 

 

 

20

DTR

Data Terminal Ready

Input to UPS - typically not used by UPS

 

 

 

 

22

–12V

–12 Volts

Output from UPS - always true

 

 

 

 

NOTE Pins 5 and 6 are tied together internally.

EATON Powerware® 9315 UPS (200–300 kVA) Operation Manual S 164201036 Rev G www.powerware.com

7−5

Page 51
Image 51
Powerware 9315 UPS operation manual Pin Assignments for Port 2 DB-25