CAUTION: Install the vent damper to service only the single appliance for which it is intended. if improperly installed, a hazardous condition, such as an explosion or carbon monoxide poisoning, could result.
Vent Damper
Normal Operation Summary
For safe, efficient operation, the vent damper and all flue product carrying areas of the appliance must be checked annually, with particular attention given to deterioration from corrosion or other sources. Check vent damper operation as follows:
1.When the boiler is off, check that the vent damper position indicator points to the closed position. (See figure below.)
2.Turn the thermostat or controller up to call for heat and check that the vent damper indicator points to the open position. (See figure below.)
3.Turn the thermostat or controller down again and check that the vent damper position indicator returns to the closed position.
NOTE: The vent damper must be inspected at least once a year by a trained, experienced service technician. The name of the person who originally installed your vent damper is shown on the installation label. Damper must be in open position when boiler main burners are operating.
Damper Position Indicator
EFFIKAL® RVGP
Fig. 21: Connection Diagram for Effikal® Vent Damper
Plumbing
Damper Open | Damper Closed |
Fig. 20: Vent Damper Position Indicator
Fig. 22: Plumbing
Gas Supply Connections
Gas piping must have a sediment trap ahead of the boiler gas controls, and a manual
NOTE: Do not use teflon tape on gas line pipe thread. A flexible sealant approved for the fuel being used is recommended.