Low Water Cut-Off (Optional)
The
Fig. 35: Low Water
High and Low Gas Pressure Switches (Optional)
NOTE: The High Gas Pressure Switch is standard on Models
These switches sense either high or low gas pres- sures and automatically shut down burners if abnormal pressures exist.
Fig. 36: Gas Pressure Switch
ELECTRICAL
CONNECTIONS
CAUTION: Label all wires prior to disconnection when servicing controls. Wiring errors can cause improper and dangerous operation. Verify proper operation after servicing.
DANGER - SHOCK HAZARD: Make sure electrical power to the heater is disconnected to avoid potential serious injury or damage to components.
This boiler is normally wired for 120 Volts. The voltage is indicated on the
DO NOT attach line voltage to the "TH" leads on mod- els
The boiler must be electrically grounded in accordance with National Electrical Code ANSI/NFPA No 70, or with CSA C22.1 C.E.C. Part 1 in Canada.
NOTES:
1.Field install ground to inside of junction box.
2.If any of the original wire as supplied with the boil- er must be replaced, it must be replaced with 105°C wire or its equivalent.
24