NOTE: If the heat exchanger is sooted badly, the burner
2.Lift burners from slotted spacer and slide from ori- fices. Clean with a wire brush.
3.Clean orifice(s) as necessary.
2.Remove front inspection panel.
3.Remove wires to high limit and loosen screws holding high limit to cabinet.
4.Remove wedge clip holding sensing bulb in con- trol well.
5.Remove high limit and install a new one.
Pilot Removal and Cleaning
1.Disconnect pilot tubing at pilot and sensor/igniter wire. Remove screws holding pilot bracket to burn- er tray.
2.Remove pilot and bracket, clean pilot of debris, small bugs, etc., with wire or small brush.
3.Replace pilot, pilot tubing, sensor ignition wires and check for leaks.
High Limit or Tankstat Removal
6.Check control operation before leaving job.
Heat Exchanger Removal
1.Shut water, gas and electricity off, close valves and relieve pressure, remove relief valve. Remove side inspection panels.
2.Remove top holding screws.
3.Remove draft diverter, lift and remove top and flue collector on stack type models. Remove inspec- tion panels.
1.Turn off electrical power.
IN/OUT
HEADER
HIGH LIMIT
4.Loosen bolts and disconnect flange nuts on in/out header, loosen union(s) at gas pipe, and slide boil- er away from piping until studs clear the heater.
ELECTRICAL
JUNCTION BOX
REDUNDANT
SAFETY
VALVE
MANUAL GAS VALVE
MAIN GAS VALVE
SEDIMENT TRAP
Fig. 53: Model
39