Raypak 133-4001 For Models with Automatic Gas Valves, Intermittent Pilot System Checkout S8600

Models: 133-4001

1 44
Download 44 pages 48.9 Kb
Page 28
Image 28
For Models with Automatic Gas Valves

For Models with Automatic Gas Valves

Lighting Instructions

1.Close all gas valves. Turn off electrical power sup- ply. Wait five (5) minutes.

2.Open manual pilot valve. Turn on electrical power. Pilot is automatically lighted.

PILOT

 

VALVE CONTROL

 

SHOWN IN THE

MAIN GAS SHUT-OFF

"ON" POSITION

VALVE SHOWN IN

 

THE "ON"

 

POSITION

GAS INLET

 

Fig. 38: Shut Off Valve

3.Open main gas valve.

4.Set temperature controls to desired temperature.

To Shut Down

Close all manual gas valves. Turn off electrical power.

Fig. 39: Ignition Module

After Start-Up

Standing Pilot Checkout

Procedure

1.Turn on pilot gas supply, light pilot, and check pilot tubing connections for leakage. With main burner in operation, paint tubing connections with a rich

soap and water solution. Bubbles indicate a gas leak.

2.Adjust pilot to obtain a normal flame enveloping 3/8 to 1/2 inch [9.5 to 12.5 mm] of the thermocou- ple or generator tip.

3.Place system in operation, and:

a.Check for satisfactory ignition of main burner.

b.Make certain the pilotstat "holds in", and that shutdown occurs within 2-1/2 minutes after the pilot flame is extinguished.

c.Observe operation for at least three cycles to be sure the system is functioning normally.

Pilot with

Burner Flame

Standing Pilot

Fig. 40: Pilot Flame Should Engulf Thermocouple

Intermittent Pilot System Checkout

(S8600)

1.Turn on power to the ignition systems and turn gas supply off.

2.Check ignition module as follows:

a.Set the thermostat or controller above room temperature to call for heat.

b.Watch for continuous spark at the pilot burner.

c.Time the spark operation. Time must be with- in the lockout timing period (15 or 90 seconds).

d.Turn thermostat down to end call for heat and wait 60 seconds on lockout models before beginning step 3.

3.Turn on gas supply.

4.Set thermostat or controller above room tempera- ture to call for heat.

5.Systems should start as follows:

a.Spark will turn on and pilot gas valve will open

28

Page 28
Image 28
Raypak 133-4001 manual For Models with Automatic Gas Valves, After Start-Up Standing Pilot Checkout Procedure, To Shut Down