size, and connections which comply with all applicable codes.
Flame Roll-Out Safety Switch
The boiler is equipped with a
Fig. 45: Flame
Service
Burner Tray Removal
COMBUSTION
AIR BLOWER
AIR SHUTTER
ADJUSTMENT
GAS
VALVE
BURNER
BURNER
HOLD-
DOWN
BRACKET
Fig. 46: Low NOx Burner Tray Assembly
1.
2.
3.Remove front door.
4.Disconnect gas line from gas valve.
5.Remove (2) screws that mount burner tray to the base of the unit, and (2) screws that secure gas valve to jacket.
6.Disconnect wires that terminate at gas valve.
7.Unscrew (4) screws that secure the control box.
8.Disconnect pilot wire from the ignition module.
9.Disconnect wire harness from the combustion blower.
10.Carefully slide out the burner tray assembly.
11.Reverse above procedure to
Gas Valve Adjustment - Robertshaw (Invensys) 7000 Series
NOTE: Attach a manometer and check the manifold pressures
1.Turn the heater off.
2.Remove the 3/8” nut or the #10 Torx screw.
3.Lift solenoid valve up, keeping the wires connect- ed to the solenoid valve.
4.If only low fire adjustment is needed, go to Step 9.
5.Using a 3/8” wrench, carefully remove the alu- minum cap that was under the solenoid
6.Remove the spring and store in a safe place.
Fig. 47: