Installation Base

Installation Base

The boiler should be mounted on a level, non-com- bustible surface. Boiler must not be installed on carpeting. The boiler can be installed on a combustible surface only when a suitable floor shield base is pro- vided. Raypak offers an optional floor shield base which can be factory installed on all indoor models except Model 133; the Model 133 floor shield base is shipped loose and must be installed by the contractor. Do NOT use the shipping crate base as an installation base.

NOTE: For Models 2100-4001, a factory-installed floor shield is standard. Table B provides the floor shield ordering information for other models.

NOTE: The boiler should be located in an area where water leakage will not result in damage to the area adjacent to the appliance or to the structure. When such locations cannot be avoided, it is recommended that a suitable drain pan, adequately drained, be installed under the appliance. The pan must not restrict air flow.

In addition, the boiler shall be installed such that the gas ignition system components are protected from water (dripping, spraying, rain, etc.) during appliance operation and service (circulator replacement, control replacement, etc.).

Boiler Model No.

Base Part No.

Boiler Model No.

Base Part No.

 

 

 

 

133

001749

926*

054597

182/181

058313

1083*

054598

260/261

058314

1178*

054599

330/331

058315

1287*

054600

400/401

058316

1414*

054601

 

 

1571*

058378

 

 

1758*

058379

 

 

 

 

514

056199

962

059233

624

056200

1125

059234

724

056201

1223

059235

824

056202

1336

059236

 

 

1468

059237

 

 

1631

059238

 

 

1826

059239

 

 

 

 

*Models with factory-installed floor shield as standard. BOLD type indicates Low NOx models.

Table B: Combustible Floor Shield Ordering

Information

Fig. 2: Alternate Method for Providing a Non-

Combustible Base

Clearances

MODEL

 

 

 

 

181 to

 

514 to

 

 

 

2100 to

 

 

 

133

 

 

926 to

 

 

 

 

401

 

824

 

1826

 

4001

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

All dimensions are in inches.

Derived from National Fuel Gas Code, Table 6.2.3(a)

*Vent includes factory-supplied drafthood and does not include field- supplied vent systems above the drafthood. On Models 2100-4001 drafthood is built into boiler.

Table C: Clearances from Combustible Surfaces

NOTE 1: Combustible floor shield is required when boiler is to be installed on a combustible surface. (See ordering information in Table B.)

NOTE 2: Servicing Clearances: Provide at least 24" (Models 133-1826), 48" (Models 2100-4001) in front of unit for removal and servicing of the Controls & Burner Tray. Provide at least 18" on side opposite water connections for deliming of Heat Exchanger Tubes.

7