INSTALLATION
CLEARANCES | COMBUSTIBLE MANTELS |
The clearances listed below are Minimum distances unless otherwise stated:
A major cause of chimney related fires is failure to maintain required clearances (air space) to combustible materials. It is of the greatest importance that this fireplace and vent system be installed only in accordance with these instructions.
Clearance to Combustibles from:
Back | 0" | (0mm) |
Side | 0" | (0mm) |
Floor | 0" | (0mm) |
NOTE: The minimum fl oor clearance must be maintained from the top surface of the carpeting, tile, etc.
Minimum Clearance from Top of Unit to:
Mantel* | min. 7" (177mm) | |
Ceiling | 30" | (762mm) |
from top of unit. |
|
|
Side Wall Clearance |
|
|
Bay or Flush Front | (191mm) |
Minimum Vent Clearances:
(Rigid Vent)
(Flex Vent)
Alcove Clearances: |
|
|
Max. Depth | 36" | (914mm) |
Min. Width | 48" | (1219mm) |
Min. Height | 59" | (1499mm) |
* see mantel clearance instructions.
Because of the extreme heat this fireplace emits, the mantel clearances are critical. Combustible mantel clearances from top of unit are shown in the diagram below.
Note: A
This drawing is to scale at 1:6 (one inch = 6 inches). Mantel can be installed anywhere in shaded area or higher using the above scale.
Note: Ensure the paint that is used on the mantel and the facing is "heat resistant" or the paint may discolour.
WARNING
Fire hazard is an extreme risk if these clearances are not adhered to.
Clearances for Bay or Flush Front
MANTEL LEG CLEARANCES
Combustible mantel leg clearances as per diagram below:
Maximum
The HeatWave Duct Kit has different clearance and framing requirements, check the HeatWave manual for details.
8 | Regency® |