INSTALLATION
UNIT INSTALLATION WITH HORIZONTAL TERMINATION
Install the vent system according to the manufacturer's instructions included with the components.
1) Set the unit in its desired location. Check |
to determine if wall studs or roof rafters |
are in the way when the venting system is |
attached. If this is the case, you may want |
to adjust the location of the unit. Rough in |
the gas preferably on the right side of the |
unit and the electrical (junction block is on |
the left side) on the left. |
2) Direct Vent pipe and fi ttings are designed |
with special |
b) Horizontal runs of | vent must be | Diagram 2a |
supported every three feet. Wall straps |
| |
are available for this | purpose. |
|
5)Mark the wall for a 10" x 10" square hole. The center of the square hole should line up with the centerline of the horizontal pipe. Cut and frame the 10 inch square hole in the exterior wall where the vent will be terminated. If the wall being penetrated is
Riser Vent
Termination
Min.
(159mm)
connect the venting system to the appliance |
fl ue outlet. A |
is an available option that must be used in |
conjunction with the Simpson |
Direct Vent GS system. |
3) Putabeadofsiliconeinsidetheoutersection |
of the adapter and a bead of Fireplace Mate |
on the inner collar. Slip the adapter over the |
existinginnerandouterfluecollarandfasten |
to the outer collar only with the 3 supplied |
screws (drilling pilot holes will make this |
easier). Level the fi replace and fasten it to |
the framing using nails or screws through |
the nailing strips. |
4) Assemble the desired combination of pipe |
and elbows to the appliance adaptor and |
Note:
a) |
located on the female ends of pipes and |
fi ttings, are designed to slide straight |
onto the male ends of adjacent pipes |
and fi ttings, by orienting the four pipe |
indentations so they match and slide |
in to the four entry slots on the male |
Note:
a)The horizontal run of vent must be level, or have a 1/4 inch rise for every 1 foot of run towards the termination. Never allow the vent to run downward. This could cause high temperatures and may present the possibility of a fi re.
b)The location of the horizontal vent terminationonanexteriorwallmustmeet all local and national building codes, and must not be blocked or obstructed. See "Exterior Vent Terminal Locations" Section.
c)Snorkel Terminations:
For installations requiring a vertical rise on the exterior of the building,
Below Grade Snorkel Installation If the Snorkel Termination must be installed below grade, i.e. basement application, proper drainage must be providedtopreventwaterfromentering the Snorkel Termination. Refer to
6)The arrow on the vent cap should be pointing up. Insure that the
ends, Dia. 1. Push the pipe sections | |
completely | together, then |
one section | clockwise approximately |
are fully locked. The female locking lugs | |
will not be visible from the outside, on | |
the Black Pipe or fi ttings. They may be | |
located by examining the inside of the | |
female ends. |
|
Diagram 1
Note: Apply sealant
lock joint.
|
Snorkel |
Min. 12"* |
(305mm) |
Diagram 2
*As specifi ed in CGA B149 Installation Code. Local codes or regulations may require different clearances.
Diagram 3
The four wood screws provided should be replaced with appropriate fasteners for stucco, brick, concrete, or other types of sidings.
Note: If installing termination on a siding covered wall, a vinyl siding standoff or furring strips must be used to ensure that the termination is not recessed into the siding.
7)Beforeconnectingthehorizontalrunofvent pipe to the vent termination, slide the Wall Thimble (Part #
24 | Regency® |