Regency P42-NG4 High Elevation, Gas Line Installation, Gas Pipe Pressure Testing, System Data

Models: P42-LP4 P42-NG4

1 48
Download 48 pages 16.72 Kb
Page 24
Image 24
System Data

INSTALLATION

System Data

For 0 to 4500 feet altitude

Burner Inlet Orifice Sizes:

Natural Gas Propane

 

Burner

#33

 

#50

 

 

 

 

 

 

 

Max. Input Rating

 

 

 

 

- Natural Gas

 

35,000

Btu/h

 

- Propane

 

35,000

Btu/h

 

Min. Input Rating

 

 

 

 

-Natural Gas

 

17500

Btu/h

 

-Propane

 

17500

Btu/h

 

 

 

 

Output Capacity with blower Off

 

Natural Gas

 

25,725

Btu/h

 

Propane

 

26,740

Btu/h

 

Output Capacity with blower On

 

Natural Gas

 

26,250

Btu/h

 

Propane

 

27,300

Btu/h

 

 

 

 

 

 

Supply Pressure

 

 

 

 

Natural Gas

min.

5.0" w.c.

 

Propane

min.

11.0" w.c.

 

 

 

 

 

Manifold Pressure (High)

 

 

 

Natural Gas

3.8"

+/- 0.2" w.c.

 

Propane

10"

+/- 0.2" w.c.

Electrical: 120 V A.C. System.

Circulation Fan: variable speed 130 CFM.

Log Set: Ceramic fi bre, 3 per set.

Vent System: Simpson Dura-Vent Direct Vent System or Regency® Direct Vent System (Flex)

Note: Output capacity. The efficiency rating of the appliance is a product thermal efficiency rating determined under continuous operating conditions and was determined independently of any installed system. Vent height may or may not change your efficiency ratings.

HIGH ELEVATION

This unit is approved in Canada for altitude 0 to 4500 ft. (CAN1 2.17-M90) with the orifi ce supplied.

GAS LINE

INSTALLATION

The gas line can be brought through either the right or the left side of the appliance. The gas valve is situated on the right hand side of the unit and the gas inlet is on the right hand side of the valve.

Note: If the gas line is being installed from the left side, be sure to leave room to accommodate servicing of the fan.

The gas line connection may be made of rigid pipe, copper pipe or an approved flex connector. (If you are using rigid pipe, ensure that the valve can be removed for servicing.) Since some municipalities have additional local codes it is always best to consult with your local authorities and the CAN/CGA B149 installation code.

For USA installations follow local codes and/or the current National Fuel Gas Code, ANSI Z223.1.

When using copper or fl ex connectors use only approved fittings.Always provide a union so that gas lines can be easily disconnected for burner or fan servicing. Flare nuts for copper lines and

ex connectors are usually considered to meet this requirement.

Important:Always check for gas leaks with a soap and water solution or gas leak detector. Do not use open flame for leak testing.

GAS PIPE PRESSURE

TESTING

The appliance must be isolated from the gas supply piping system by closing its individual manual shut-off valve during any pressure testing of the gas supply piping system at test pressures equal to or less than 1/2 psig. (3.45 kPa). Disconnect piping from valve at pressures over 1/2 psig (3.45 kPa).

Themanifoldpressureiscontrolledbyaregulator built into the gas control, and should be checked at the pressure test point.

Note: To properly check gas pressure, both inlet and manifold pressures should be checked using the valve pressure ports on the valve.

1)Make sure the valve is in the "OFF" position.

2)Loosen the "IN" and/or "OUT" pressure tap(s), turning counterclockwise with a 1/8" (3mm) wide fl at screwdriver.

3)Attach manometer to "IN" and/or "OUT" pressure tap(s) using a 5/16" (8mm) ID hose.

4)Light the pilot and turn the valve to "ON" position.

5)The pressure check should be carried out with the unit burning and the setting should be within the limits specifi ed on the safety label.

6)When fi nished reading manometer, turn off the gas valve, disconnect the hose and tighten the screw (clockwise) with a 1/8"(3mm) fl at screwdriver. Note: Screw should be snug, but do not over tighten.

S.I.T. Valve Description

1)Gas on/off knob

2)Manual high/low adjustment

3)Pilot Adjustment

4)Thermocouple Connection - option

5)Outlet Pressure Tap

6)Inlet Pressure Tap

7)Pilot Outlet

8)Main Gas Outlet

9)Alternative TC Connection Point

24

Regency® P42-4 Zero Clearance Direct Vent Gas Fireplace

Page 24
Image 24
Regency P42-NG4 High Elevation, Gas Line Installation, Gas Pipe Pressure Testing, System Data, S.I.T. Valve Description