REMINGTON QFP40 Direct Vent FIREPLACE

HORIZONTAL TERMINATION REQUIREMENTS

A.*12” (30cm) minimum: Clearance above grade, veranda, porch, deck, or balcony.

B.*12” (30cm) minimum: Clearance to window or door that may be opened.

C.12” (30cm) minimum: Clearance to permanently closed window (recommended to prevent condensation on window.

D.18” (46cm) minimum: Vertical clearance to ventilated soffit located above the terminal within a horizontal distance of 2’ (60cm) from the centerline of the terminal.

E.12” (30)cm) minimum: Clearance to unventilated soffit.

F.6” (15cm): Clearance to outside corner.

G.9” (23cm): Clearance to inside corner.

*Not to be installed above a meter/regulator (gas or electrical) assembly within 3’ (90cm) horizontally from the centerline of the meter/regulator.

H.*6’ (1.8m) minimum: Clearance to service regulator vent outlet.

I.*12” (30cm) minimum: Clearance to nonmechanical air supply inlet to building or the combustion air inlet to any other appliance.

J.*6’ (1.8m) minimum: Clearance to a mechanical air supply air inlet.

K.*+7’ (2.1m) minimum: Clearance above paved sidewalk or a paved driveway located on public property.

L.*#12” (30 cm) minimum: Clearance under veranda, porch, deck, or balcony.

M.6” (15 cm) minimum: Clearance to adjacent building or deck.

N.6” (15 cm) minimum: Clearance to nearby building

+A vent shall not terminate directly above a sidewalk or paved driveway which is located between two single-family dwellings and serves both dwellings.*

#Only permitted if veranda, porch, deck, or balcony, is fully open on a minimum of two sides beneath the floor.*

*As specified in CGA B149 Installation Codes

Note: Local Codes or regulations may require different clearances.