Roberts Gorden BH15UT, BH35UT/EF, BH40DL U-Tube, Troubleshooting Flow Chart Linear, Double Linear

Models: BH45ST/EF BH20UT BH50ST/EF BH55ST BH70DL/EF BH45UT/EF BH50UT/EF BH40UT/EF BH30DL BH15UT BH25ST/EF BH30ST/EF BH50DL/EF BH40ST/EF BH15ST BH20ST BH25UT/EF BH60DL/EF BH35ST/EF BH40DL BH30UT/EF BH35UT/EF

1 84
Download 84 pages 15.61 Kb
Page 71
Image 71

 

 

Replace ignition

No

 

 

module.

 

 

 

Turn up thermostat.

No

Place a jumper across

No

the thermostat terminals.

Does the fan turn on?

 

Does the fan turn on?

 

 

 

 

 

 

Yes

 

 

 

Check thermostat wiring

 

 

 

and replace thermostat if

 

 

 

necessary.

 

Yes

Is there power out

from pin 10 on

ignition module?

Yes

Is there power (230V)

at the burner?

No

Check relay wiring

(if applicable) and wiring

to the burner.

Yes

Remove Black & White

leads from the pressure switch; No place jumper between leads.

Does the fan turn on?

Yes

Replace pressure switch.

Remove obstruction.

Yes

Replace Fan.

Yes

Unplug burner.

Does the fan turn freely?

No

Is the fan obstructed?

No

Fan bearings may have

failed. Replace fan.

16.1 Troubleshooting Flow Chart (Linear, Double Linear

Unplug burner and check

Is there spark at the igniter? No electrode and ignition wire. No

Are they damaged?

Yes

Replace electrode and ignition wire as needed.

65 of 75

Is the igniter gap

set at 3 mm?

No

Carefully reset gap

to 3 mm.

Replace automatic

control unit.

Yes

Is the flue pipe or

Yes

the inlet of the

 

burner obstructed?

 

 

No

 

Are the hoses to the pressure No switch secure and leak free?

Yes

Remove Black and Yellow No leads from the pressure switch;

place a jumper between leads.

Is there a spark?

Yes

Replace pressure switch.

Remove obstruction.

Repair, replace or

tighten hoses as necessary.

and U-Tube)

SECTION 16: TROUBLESHOOTING

Page 71
Image 71
Roberts Gorden BH15UT, BH35UT/EF, BH30UT/EF, BH40DL, BH35ST/EF U-Tube, Troubleshooting Flow Chart Linear, Double Linear