Roberts Gorden BH40UT/EF, BH35UT/EF, BH30UT/EF Troubleshooting Flow Chart Multiburner, 67 of

Models: BH45ST/EF BH20UT BH50ST/EF BH55ST BH70DL/EF BH45UT/EF BH50UT/EF BH40UT/EF BH30DL BH15UT BH25ST/EF BH30ST/EF BH50DL/EF BH40ST/EF BH15ST BH20ST BH25UT/EF BH60DL/EF BH35ST/EF BH40DL BH30UT/EF BH35UT/EF

1 84
Download 84 pages 15.61 Kb
Page 73
Image 73
16.2 Troubleshooting Flow Chart (Multiburner)

Turn up thermostat.

No

Is there power (230V)

Yes

to the control panel?

Does the fan turn on?

 

 

 

 

 

No

 

Check thermostat

and replace if

necessary.

Check clock program.

Reset as required.

No

Is the clock set to on?

Fan motor may have to

be replaced.

 

Is there power output

 

Refer to control panel

 

 

Yes

No

IOS manual for

 

 

to the fan?

 

 

 

 

troubleshooting.

 

 

 

Yes

 

 

 

 

 

 

 

 

 

Disconnect power to the

 

Motor may have have tripped

 

Is the motor connected

 

Yes

overload switch. Wait

No

properly? Refer to the wiring

 

motor. Does the

 

10 - 15 minutes for

diagrams on the motor and

 

motor turn freely?

 

 

 

 

automatic reset.

 

in the installation manual.

 

No

 

 

 

 

 

 

 

No

Is there an obstruction to

Yes

Remove obstruction.

 

 

the pump impeller?

 

 

 

 

 

 

 

16.2 Troubleshooting Flow Chart (Multiburner)

Yes

 

 

 

After 20 second pre-purge

 

Unplug burner and check

 

No

electrode and ignition wire.

No

Is there spark at the igniter?

 

 

Are they damaged?

 

 

 

Yes

 

 

 

Replace electrode and

 

 

 

ignition wire as needed.

 

Is the igniter gap

 

Is the flue pipe or

 

Yes

the inlet of the

Yes

set at 3 mm?

 

burner obstructed?

 

 

 

 

No

 

No

 

Carefully reset gap

 

Are the hoses to the pressure

No

to 3 mm.

 

switch secure and leak free?

 

 

 

Yes

 

Remove obstruction.

Repair, replace or

tighten hoses as necessary.

67 of 75

Replace automatic

control unit.

Remove Black and Yellow No leads from the pressure switch;

place a jumper between leads.

Is there a spark?

Yes

Replace pressure switch.

SECTION 16: TROUBLESHOOTING

Page 73
Image 73
Roberts Gorden BH40UT/EF, BH35UT/EF, BH30UT/EF, BH40DL, BH35ST/EF, BH60DL/EF Troubleshooting Flow Chart Multiburner, 67 of