68 of 74

Yes

Do all burners light?

No

Yes

 

Do the burners

No

stay on?

 

Yes

Were the gas lines

No

purged of air correctly?

 

Yes

 

Is there sufficient inlet gas pressure (See Specification Yes

Section) during ignition?

No

Check gas line stop cock. Check gas supply at meter.

Contact gas company.

Is the continuity of the

Yes

earth wire established?

 

No

 

Re-establish continuity.

Purge Lines.

Measure voltage on valve terminals. Is there 230 V during ignition time?

No

Are the wires connecting the automatic control unit OK?

Yes

Replace automatic

control unit.

Are the Live and Neutral

reversed?

Yes

Reverse polarity.

Check for the proper jet and air plate inside the burner.

Yes

Is the gas outlet pressure

in accordance with

Specifications Section

of this manual?

Yes

Is there gas outlet pressure

Yes available during the ignition period?

No

Replace/Correct wires.

Is the wiring at the

No module properly connected?

No

Re-establish connections.

No

No

Yes

Adjust the governor

pressure.

Replace solenoid

coil.

Ignition module may have failed. Replace module.

Yes

Is the insulation on the electrode/sensor leads OK?

No

Replace/Correct

Wires.

Troubleshooting Flow Chart (Multiburner)

BLACKHEAT® INSTALLATION OPERATION AND SERVICE MANUAL

Is the system leaking water? Yes

No

 

Do the burners turn off

No

when the call for heat ends?

Yes

 

TROUBLESHOOT ENDS.

If problems persist, contact

Roberts-Gordon at

Tel: +44 (0)121 506 7700 or

Fax: +44 (0)121 506 7701 or

online at www.rg-inc.com

Is the vacuum setting

 

Are there any "dead" burners

 

Is the rotation of the pump

 

Manifold ID/ID Connectors

No

No

Yes

may be installed improperly.

too low?

 

in a branch?

 

motor correct?

 

High temperature silicone

Yes

 

Yes

 

No

 

sealant should be used at

 

 

 

all connections.

Adjust system for proper

 

Follow burner check

 

Consult venting and wiring

 

 

vacuum. See

 

 

sections of this manual

 

 

 

procedure given above.

 

 

 

Specification Section.

 

 

for reversal instructions.

 

 

 

 

 

 

 

Check the

 

 

 

 

 

 

control panel.

 

 

 

 

 

 

Page 74
Image 74
Roberts Gorden BH50UT/EF, BH35UT/EF, BH30UT/EF Troubleshooting Flow Chart Multiburner, Re-establish continuity Purge Lines